Danfoss VLT AQUA Drive FC 202 Programming Manual page 199

Software version: 3.30
Hide thumbs Also See for VLT AQUA Drive FC 202:
Table of Contents

Advertisement

Parameter Description
23-50 Energy Log Resolution
Option:
Function:
Week, or [2] Day of Month. The counters
contain the logging data from the
programmed date/time for start
(parameter 23-51 Period Start) and the
numbers of hours/days as programmed for
(parameter 23-50 Energy Log Resolution).
The logging starts on the date programmed
in parameter 23-51 Period Start and continues
until 1 day/week/month has passed. The
counters contain data for 1 day, 1 week, or 5
weeks back in time, and up to the actual
time.
The logging starts at the date programmed
in parameter 23-51 Period Start. In all cases,
the period split refers to operating hours
(time where frequency converter is powered
up).
[0]
Hour of Day
[1]
Day of Week
[2]
Day of
Month
[5]
Last 24
*
Hours
[6]
Last 7 Days
[7]
Last 5
Weeks
23-51 Period Start
Range:
Function:
NOTICE
Size
[ 0 -
related
0 ]
*
When mounting VLT
MCB 109, a battery back-up of the date
and time is included.
Set the date and time at which the energy log
starts updating the counters. First, data is
stored in counter [00] and start at the time/
date programmed in this parameter.
Date format depends on setting in
parameter 0-71 Date Format and time format
on setting in parameter 0-72 Time Format.
23-53 Energy Log
Array [31]
Range:
Function:
NOTICE
0
[0 -
*
4294967295 ]
All counters are automatically reset
when changing the setting in
parameter 23-50 Energy Log Resolution.
At overflow, the update of the counters
stops at maximum value.
MG20OB02
Programming Guide
23-53 Energy Log
Array [31]
Range:
®
Analog I/O option
23-54 Reset Energy Log
Option:
[0]
[1]
Danfoss A/S © 05/2018 All rights reserved.
Function:
NOTICE
When mounting VLT
MCB 109 option card, a battery back-up
of the date and time is included.
Array with several elements equal to the
number of counters ([00]-[xx] below parameter
number in display). Press [OK] and step
between elements with [
Array elements:
Ener gy met er
23-53 Ener gy met er
(03)
Ener gy met er
23-53 Ener gy met er
(02)
Ener gy met er
23-53 Ener gy met er
(01)
Ener gy met er
23-53 Ener gy met er
(00)
Illustration 3.76 Energy Log
Data from the latest period is stored in the
counter with the highest index.
At power-down, all counter values are stored
and resumed at next power-up.
Function:
Select [1] Do reset to reset all values in the
energy log counters shown in
parameter 23-53 Energy Log. After pressing OK,
the setting of the parameter value automatically
changes to [0] Do not reset.
Do not
*
reset
Do reset
®
Analog I/O Option
] and [
].
Ener gy met er
23-5*
23-53 Ener gy met er
(06)
Ener gy met er
23-5*
23-53 Ener gy met er
(05)
Ener gy met er
23-5*
23-53 Ener gy met er
(04)
23-5*
23-5*
23-5*
23-5*
197