Parameter Description
27-44 Destaging Threshold
Range:
3
3
Motor speed
high
Destaging
speed
(27-44)
Motor speed
low
Illustration 3.108 Destaging Threshold
27-45 Staging Speed [RPM]
Range:
0 RPM
[0 - 0 RPM] Shows the actual staging speed based on
*
27-46 Staging Speed [Hz]
Range:
0 Hz
[0 - 0 Hz] Shows the actual staging speed based on the
*
27-47 Destaging Speed [RPM]
Range:
0 RPM
[0 - 0 RPM] Shows the actual destaging speed based
*
27-48 Destaging Speed [Hz]
Range:
0 Hz
[0 - 0 Hz] Shows the actual destaging speed based on
*
3.24.9 27-5* Alternation Settings
Parameters for configuring the alternation settings.
27-51 Alternation Event
Select option [1] At Destage to enable alternation at destaging.
Option:
[0]
[1]
27-52 Alternation Time Interval
Range:
0 min
[0 -
*
10080
min]
230
VLT
Function:
LCP, then the new values are used, but are
continuously automatically tuned.
Closed loop
Variable speed
pump
Monitor feedback and
change to closed loop if
Fixed speed pump
setpoint is reached
Function:
the staging threshold.
Function:
staging threshold.
Function:
on the destaging threshold.
Function:
the destaging threshold.
Function:
Off
At Destage
Function:
Enter the time between alternations. Disable
the alternation by entering the value 0.
Parameter 27-53 Alternation Timer Value
shows the time remaining until the next
alternation occurs.
Danfoss A/S © 05/2018 All rights reserved.
®
AQUA Drive FC 202
27-53 Alternation Timer Value
Range:
0 min
[0 - 10080
*
min]
27-54 Alternation At Time of Day
Enable alternating pumps at a specific time of day. The time is
set in parameter 27-55 Alternation Predefined Time. This parameter
requires the real-time clock.
Option:
[0]
*
Time
[1]
27-55 Alternation Predefined Time
Range:
Size
related
*
27-56 Alternate Capacity is <
Range:
0 %
[0 -
*
100 %]
27-58 Run Next Pump Delay
Range:
0.1 s
[0.1 - 5 s] Enter the delay between stopping the current
*
Illustration 3.109 Run Next Pump Delay
Function:
Shows the time remaining before an
interval-based alternation occurs.
Parameter 27-52 Alternation Time Interval
defines the time interval.
Function:
Disabled
Enabled
Function:
[ 0 -
Enter the time of day for pump alternation.
0 ]
This parameter is only available if
parameter 27-54 Alternation At Time of Day is
set to option [1] Enabled.
Function:
This parameter ensures that the lead pump is
operating at a speed lower than a certain value
before the time-based alternation takes place.
This ensures that alternation only takes place
when the interruption in operation does not
affect the quality of the process and minimizes
the system disturbance caused by alternations.
The value is a percentage of the capacity of
pump 1. Setting this parameter to 0% disables it.
Function:
lead pump and starting the next lead pump
when alternating lead pumps. This parameter
gives the contactors time to switch while both
pumps are stopped.
(27-58)