Parameter Description
8-55 Set-up Select
Select the trigger for the set-up selection.
Option:
Function:
[0]
Digital input A digital input triggers the set-up selection.
[1]
Bus
A serial communication port or the fieldbus
triggers the set-up selection.
[2]
Logic AND
The fieldbus/serial communication port and a
digital input trigger the set-up selection.
[3]
Logic OR
The fieldbus/serial communication port or a
*
digital input triggers the set-up selection.
8-56 Preset Reference Select
Option:
Function:
Select the trigger for the preset reference
selection.
[0]
Digital
A digital input triggers the preset reference
input
selection.
[1]
Bus
A serial communication port or the fieldbus
triggers the preset reference selection.
[2]
Logic AND
The fieldbus/serial communication port and a
digital input trigger the preset reference
selection.
[3]
Logic OR
The fieldbus/serial communication port or a
*
digital input triggers the preset reference
selection.
3.9.6 8-8* FC Port Diagnostics
These parameters are used for monitoring the bus
communication via the frequency converter port.
8-80 Bus Message Count
Range:
Function:
0
[0 - 4294967295 ] This parameter shows the number of
*
valid telegrams detected on the bus.
8-81 Bus Error Count
Array [6]
Range:
Function:
0
[0 - 4294967295 ] This parameter shows the number of
*
telegrams with faults (for example CRC
fault) detected on the bus.
8-82 Slave Message Rcvd
Range:
Function:
0
[0 - 4294967295 ] This parameter shows the number of
*
valid telegrams addressed to the slave
sent by the frequency converter.
MG20OB02
Programming Guide
8-83 Slave Error Count
Range:
0
[0 - 4294967295 ] This parameter shows the number of
*
3.9.7 8-9* Bus Jog
8-94 Bus Feedback 1
Range:
0
[-200 -
*
200 ]
8-95 Bus Feedback 2
Range:
0
[-200 - 200 ] See parameter 8-94 Bus Feedback 1 for further
*
8-96 Bus Feedback 3
Range:
0
[-200 - 200 ] See parameter 8-94 Bus Feedback 1 for further
*
8-97 Response Error Codes
Range:
0
*

3.10 Parameters 9-** PROFIBUS

For PROFIBUS parameter descriptions, see the VLT
PROFIBUS DP MCA 101 Programming Guide.
Danfoss A/S © 05/2018 All rights reserved.
Function:
error telegrams, which are not executed
by the frequency converter.
Function:
Write feedback to this parameter via the serial
communication port or fieldbus option. Select
this parameter as a feedback source in
parameter 20-00 Feedback 1 Source,
parameter 20-03 Feedback 2 Source, or
parameter 20-06 Feedback 3 Source.
Function:
details.
Function:
details.
Function:
[0 - 0 ]
3
3
®
109