Parameter Description
0-13 Readout: Linked Set-ups
Array [5]
Range:
0
[0 -
*
255 ]
3
3
0-14 Readout: Prog. Set-ups / Channel
Range:
0
[-2147483648
*
- 2147483647 ]
3.2.3 0-2* LCP Display
Define the variables shown in the LCP.
NOTICE
For information on how to write display texts, refer to:
Parameter 0-37 Display Text 1.
Parameter 0-38 Display Text 2.
Parameter 0-39 Display Text 3.
0-20 Display Line 1.1 Small
Option:
[0]
None
[953]
Profibus
Warning Word
30
Function:
View a list of all the set-ups linked by
parameter 0-12 This Set-up Linked to. The parameter
has 1 index for each parameter set-up. The value
for each index shows which set-ups are linked to
that parameter set-up.
Index
LCP value
0
{0}
1
{1,2}
2
{1,2}
3
{3}
4
{4}
Table 3.2 Set-up Link Example
Function:
View the setting of
parameter 0-11 Programming Set-up for each
of the 4 different communication channels.
When the number is shown in hex, as it is in
the LCP, each number shows 1 channel.
Numbers 1–4 show a set-up number; F
stands for the factory setting, and A stands
for an active set-up. The channels are, from
right to left: LCP, fieldbus, USB, HPFB1.5.
Example: The value AAAAAA21h means that
the fieldbus channel uses set-up 2 in
parameter 0-11 Programming Set-up, the LCP
uses set-up 1, and all other channels use the
active set-up.
Function:
Select a variable to show in line 1, left
position.
No display value selected
Shows PROFIBUS communication
warnings.
Danfoss A/S © 05/2018 All rights reserved.
®
VLT
AQUA Drive FC 202
0-20 Display Line 1.1 Small
Option:
[1005]
[1006]
[1007]
[1013]
[1230]
[1472]
[1473]
[1474]
[1501]
[1502]
[1600]
[1601]
[1602]
[1603]
[1605]
[1609]
[1610]
[1611]
[1612]
Function:
Readout
Shows the number of CAN control
Transmit Error
transmission errors since the last power-
Counter
up.
Readout
Shows the number of CAN control
Receive Error
receipt errors since the last power-up.
Counter
Readout Bus
Shows the number of bus-off events
Off Counter
since the last power-up.
Warning
Shows a DeviceNet-specific warning
Parameter
word. One separate bit is assigned to
every warning.
Warning
Parameter
VLT Alarm
Word
VLT Warning
Word
VLT Ext. Status
Word
Running Hours
View the number of running hours of
the motor.
kWh Counter
View the mains power consumption in
kWh.
Control Word
View the control word sent from the
frequency converter via the serial
communication port in hex code.
Reference
Total reference (sum of digital, analog,
[Unit]
preset, bus, freeze reference, catch up,
and slow down) in selected unit.
Reference %
Total reference (sum of digital, analog,
preset, bus, freeze reference, catch up,
and slow down) in percent.
Status Word
Present status word.
Main Actual
One or more warnings in hex code.
Value [%]
Custom
View the user-defined readouts as
Readout
defined in:
Parameter 0-30 Custom Readout
Unit.
Parameter 0-31 Custom Readout
Min Value.
Parameter 0-32 Custom Readout
Max Value.
Power [kW]
Actual power consumed by the motor
in kW.
Power [hp]
Actual power consumed by the motor
in hp.
Motor Voltage
Voltage supplied to the motor.
MG20OB02