Parameter Description
16-86 FC Port REF 1
Range:
0
[-200 -
*
200 ]
3
3
16-89 Configurable Alarm/Warning Word
Range:
0
[0 - 65535 ] Shows the alarm/warning word that is
*
3.15.7 16-9* Diagnosis Readouts
NOTICE
When using MCT 10 Set-up Software, the readout
parameters can only be read online, that is as the actual
status. This means that the status is not stored in the
MCT 10 Set-up Software file.
16-90 Alarm Word
Range:
0
[0 - 4294967295 ] Show the alarm word sent via the serial
*
16-91 Alarm Word 2
Range:
0
[0 - 4294967295 ] View the alarm word 2 sent via the serial
*
16-92 Warning Word
Range:
0
[0 - 4294967295 ] Show the warning word sent via the
*
16-93 Warning Word 2
Range:
0
[0 - 4294967295 ] View the warning word 2 sent via the
*
16-94 Ext. Status Word
Range:
0
[0 - 4294967295 ] Returns the extended status word sent
*
16-95 Ext. Status Word 2
Range:
0
[0 - 4294967295 ] Returns the extended warning word 2
*
154
VLT
Function:
View the 2-byte status word (STW) sent to the
fieldbus master. Interpretation of the status word
depends on the fieldbus option installed and the
control word profile selected in
parameter 8-10 Control Profile.
Function:
configured in parameter 8-17 Configurable
Alarm and Warningword.
Function:
communication port in hex code.
Function:
communication port in hex code.
Function:
serial communication port in hex code.
Function:
serial communication port in hex code.
Function:
via the serial communication port in hex
code.
Function:
sent via the serial communication port in
hex code.
Danfoss A/S © 05/2018 All rights reserved.
®
AQUA Drive FC 202
16-96 Maintenance Word
Range:
0
[0 -
*
4294967295 ]
Function:
Readout of the preventive maintenance word.
The bits reflect the status for the
programmed preventive maintenance events
in parameter group 23-1* Maintenance. 13 bits
show combinations of all the possible items:
•
Bit 0: Motor bearings.
•
Bit 1: Pump bearings.
•
Bit 2: Fan bearings.
•
Bit 3: Valve.
•
Bit 4: Pressure transmitter.
•
Bit 5: Flow transmitter.
•
Bit 6: Temperature transmitter.
•
Bit 7: Pump seals.
•
Bit 8: Fan belt.
•
Bit 9: Filter.
•
Bit 10: Frequency converter cooling
fan.
•
Bit 11: Frequency converter system
health check.
•
Bit 12: Warranty.
•
Bit 13: Maintenance Text 0.
•
Bit 14: Maintenance Text 1.
•
Bit 15: Maintenance Text 2.
•
Bit 16: Maintenance Text 3.
•
Bit 17: Maintenance Text 4.
•
Bit 25: Service log full.
MG20OB02
Need help?
Do you have a question about the VLT AQUA Drive FC 202 and is the answer not in the manual?
Questions and answers