Parameter Description
8-13 Configurable Status Word STW
This parameter enables configuration of bits 12–15 in the status
word.
Array [16]
Option:
Function:
[72]
Logic Rule 2
See parameter group 13-4* Logic Rules. If
logic rule 2 is evaluated as true, the
output goes high. Otherwise, it is low.
[73]
Logic Rule 3
See parameter group 13-4* Logic Rules. If
logic rule 3 is evaluated as true, the
output goes high. Otherwise, it is low.
[74]
Logic Rule 4
See parameter group 13-4* Logic Rules. If
logic rule 4 is evaluated as true, the
output goes high. Otherwise, it is low.
[75]
Logic Rule 5
See parameter group 13-4* Logic Rules. If
logic rule 5 is evaluated as true, the
output goes high. Otherwise, it is low.
[80]
SL digital out A
See parameter 13-52 SL Controller Action.
The output goes high whenever the
smart logic action [38] Set digital out A
high is executed. The output goes low
whenever the smart logic action [32] Set
digital out A low is executed.
[81]
SL digital out B
See parameter 13-52 SL Controller Action.
The output goes high whenever the
smart logic action [39] Set digital out B
high is executed. The output goes low
whenever the smart logic action [33] Set
digital out B low is executed.
[82]
SL digital out C
See parameter 13-52 SL Controller Action.
The output goes high whenever the
smart logic action [40] Set digital out C
high is executed. The output goes low
whenever the smart logic action [34] Set
digital out C low is executed.
[83]
SL digital out D
See parameter 13-52 SL Controller Action.
The output goes high whenever the
smart logic action [41] Set digital out D
high is executed. The output goes low
whenever the smart logic action [35] Set
digital out D low is executed.
[84]
SL digital out E
See parameter 13-52 SL Controller Action.
The output goes high whenever the
smart logic action [42] Set digital out E
high is executed. The output goes low
whenever the smart logic action [36] Set
digital out E low is executed.
[85]
SL digital out F
See parameter 13-52 SL Controller Action.
The output goes high whenever the
smart logic action [43] Set digital out F
high is executed. The output goes low
whenever the smart logic action [37] Set
digital out F low is executed.
MG20OB02
Programming Guide
8-13 Configurable Status Word STW
This parameter enables configuration of bits 12–15 in the status
word.
Array [16]
Option:
[86]
ATEX ETR cur.
alarm
[87]
ATEX ETR freq.
alarm
[88]
ATEX ETR cur.
warning
[89]
ATEX ETR freq.
warning
[181] Prev.
Maintenance
[182] Deragging
[183] Post/Pre Lube
[190] No-Flow
[191] Dry Pump
[192] End Of Curve
[193] Sleep Mode
[194] Broken Belt
[196] Emergency
Mode
[197] Emerg. Mode
was Act.
[199] Pipe Filling
[200] User Defined
Alerts
8-14 Configurable Control Word CTW
Array [15]
Option:
[0]
None
[1]
Profile
*
default
[2]
CTW Valid,
active low
8-17 Configurable Alarm and Warningword
Array [16]
Select the meaning of a specific bit in the configurable alarm
and warning word. The word has 16 bits (0–15).
Option:
[0]
*
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
Danfoss A/S © 05/2018 All rights reserved.
Function:
Function:
The frequency converter ignores the
information in this bit.
The functionality of the bit depends on the
selection parameter 8-10 Control Word Profile.
If set to 1, the frequency converter ignores
the remaining bits of the control word.
Off
10 Volts low warning
Live zero warning
No motor warning
Mains phase loss warning
DC link voltage high warning
DC link voltage low warning
DC overvoltage warning
DC undervoltage warning
3
3
Function:
103