Parameters 16-** Data Readouts - Danfoss VLT AQUA Drive FC 200 Programming Manual

Hide thumbs Also See for VLT AQUA Drive FC 200:
Table of Contents

Advertisement

Parameter Description

3.15 Parameters 16-** Data Readouts

16-00 Control Word
Range:
0
[0 - 65535 ] View the Control word sent from the
*
3
3
16-01 Reference [Unit]
Range:
0.000 Reference-
FeedbackUnit
*
16-02 Reference [%]
Range:
0.0 %
[-200.0 -
*
200.0 %]
16-03 Status Word
Range:
0
[0 - 65535 ] View the Status word sent from the frequency
*
16-05 Main Actual Value [%]
Range:
0.00 %
[-100.00 -
*
100.00 %]
16-09 Custom Readout
Range:
0.00 CustomRea-
doutUnit
*
118
VLT
Function:
frequency converter via the serial communi-
cation port in hex code.
Function:
[-999999.000 -
View the present
999999.000
reference value applied
ReferenceFeed-
on impulse or analog
backUnit]
basis in the unit
resulting from the
configuration selected
in 1-00 Configuration
Mode (Hz, Nm or RPM).
Function:
View the total reference. The total
reference is the sum of digital, analog,
preset, bus, and freeze references, plus
catch-up and slow-down.
Function:
converter via the serial communication port in
hex code.
Function:
View the two-byte word sent with the
Status word to the bus Master
reporting the Main Actual Value. Refer
to the Profibus Operating Instructions
MG33C for further details.
Function:
[-999999.99 -
View the user-defined
999999.99
readouts as defined in
CustomRea-
0-30 Custom Readout Unit,
doutUnit]
0-31 Custom Readout Min
Value and 0-32 Custom
Readout Max Value.
MG20O602 - VLT
®
AQUA Drive Programming Guide
3.15.1 16-1* Motor Status
16-10 Power [kW]
Range:
0.00
[0.00 -
kW
10000.00
*
kW]
16-11 Power [hp]
Range:
0.00
[0.00 -
hp
10000.00 hp]
*
16-12 Motor Voltage
Range:
0.0 V
[0.0 - 6000.0 V] View the motor voltage, a calculated
*
16-13 Frequency
Range:
0.0 Hz
[0.0 - 6500.0 Hz] View the motor frequency, without
*
16-14 Motor Current
Range:
0.00 A
[0.00 -
*
10000.00 A]
16-15 Frequency [%]
Range:
0.00
[-100.00 -
%
100.00 %]
*
®
is a registered Danfoss trademark
Function:
Displays motor power in kW. The value
shown is calculated on the basis of the
actual motor voltage and motor current.
The value is filtered, and therefore approx.
30 ms may pass from when an input value
changes to when the data read-out values
change. The resolution of read-out value
on fieldbus is in 10 W steps.
Function:
View the motor power in HP. The value
shown is calculated on the basis of the
actual motor voltage and motor current.
The value is filtered, and therefore
approximately 30 ms may pass from
when an input value changes to when
the data read-out values change.
Function:
value used for controlling the motor.
Function:
resonance dampening.
Function:
View the motor current measured as a
mean value, I
. The value is filtered,
RMS
and thus approximately 30 ms may pass
from when an input value changes to
when the data read-out values change.
Function:
View a two-byte word reporting the
actual motor frequency (without
resonance dampening) as a percentage
(scale 0000-4000 Hex) of 4-19 Max Output
Frequency. Set 9-16 PCD Read Configu-
ration index 1 to send it with the Status
Word instead of the MAV.