Parameter Description
16-55 Feedback 2 [Unit]
Range:
0
ProcessCtrlUnit
3
3
16-56 Feedback 3 [Unit]
Range:
0 ProcessCtrlUnit
16-58 PID Output [%]
Range:
0 %
[0 - 100 %] This parameter returns the frequency
*
16-59 Adjusted Setpoint
Range:
0 ProcessCtrlUnit
3.15.5 16-6* Inputs and Outputs
16-60 Digital Input
Range:
0
[0 -
N/A
1023
N/A]
*
152
Function:
[-999999.999 -
View value of feedback 2, see
999999.999
parameter group 20-0*
*
ProcessCtrlUnit]
Feedback.
The unit is set in
parameter 20-12 Reference/
Feedback Unit.
Function:
[-999999.999 -
View value of
*
999999.999
feedback 3, see
ProcessCtrlUnit]
parameter group 20-0*
Feedback.
Function:
converter closed-loop PID controller output
value in percent.
Function:
[-999999.999 -
Shows the value of
*
999999.999
the adjusted
ProcessCtrlUnit]
setpoint.
Function:
View the signal states from the active digital
inputs. For example, input 18 corresponds to bit
5. 0=No signal, 1=connected signal.
Bit 0
Digital input terminal 33.
Bit 1
Digital input terminal 32.
Bit 2
Digital input terminal 29.
Bit 3
Digital input terminal 27.
Bit 4
Digital input terminal 19.
Bit 5
Digital input terminal 18.
Bit 6
Digital input terminal 37.
Bit 7
Digital input GP I/O terminal
X30/4.
Bit 8
Digital input GP I/O terminal
X30/3.
Bit 9
Digital input GP I/O terminal
X30/2.
Bits 10–63
Reserved for future terminals.
Table 3.26 Digital Input Bits
Danfoss A/S © 05/2018 All rights reserved.
®
VLT
AQUA Drive FC 202
16-61 Terminal 53 Switch Setting
Option:
[0]
Current
*
[1]
Voltage
16-62 Analog Input 53
Range:
0
[-20 - 20 ]
*
16-63 Terminal 54 Switch Setting
View the setting of input terminal 54.
Option:
[0]
*
[1]
16-64 Analog Input 54
Range:
0
[-20 - 20 ]
*
16-65 Analog Output 42 [mA]
Range:
0
[0 - 30 ] View the actual value at output 42 in mA. The
*
16-66 Digital Output [bin]
Range:
0
[0 - 15 ]
*
16-67 Freq. Input #29 [Hz]
Range:
0 N/A
*
16-68 Freq. Input #33 [Hz]
Range:
0 N/A
*
16-69 Pulse Output #27 [Hz]
Range:
0 N/A
*
16-70 Pulse Output #29 [Hz]
Range:
0 N/A
*
Function:
View the setting of input terminal 53.
Function:
View the actual value at input 53.
Function:
Current
Voltage
Function:
View the actual value at input 54.
Function:
value shown reflects the selection in
parameter 6-50 Terminal 42 Output.
Function:
View the binary value of all digital outputs.
Function:
[0 - 130000 N/A] View the actual frequency rate on
terminal 29.
Function:
[0 - 130000 N/A] View the actual frequency rate on
terminal 33.
Function:
[0 - 40000 N/A] View the actual value on terminal 27 in
digital output mode.
Function:
[0 - 40000 N/A] View the actual value of pulses on
terminal 29 in digital output mode.