Danfoss VLT AQUA Drive FC 202 Programming Manual page 104

Software version: 3.30
Hide thumbs Also See for VLT AQUA Drive FC 202:
Table of Contents

Advertisement

Parameter Description
3.9.2 8-1* Ctrl. Word Settings
8-10 Control Profile
Select the interpretation of the control and status words
corresponding to the installed fieldbus. Only the selections valid
3
3
for the fieldbus installed in slot A are visible in the LPC display.
For guidelines in selection of [0] Frequency converter profile and
[1] PROFIdrive profile, refer to the design guide of the related
product. For more guidelines in the selection of [1] PROFIdrive
profile, [5] ODVA, and [7] CANopen DSP 402, see the installation
guide for the installed fieldbus.
Option:
[0]
*
[1]
[5]
[7]
8-13 Configurable Status Word STW
This parameter enables configuration of bits 12–15 in the status
word.
Array [16]
Option:
[0]
No function
[1]
Profile Default
*
[2]
Alarm 68 Only
[3]
Trip excl Alarm
68
[10]
T18 DI status
[11]
T19 DI status
[12]
T27 DI status
[13]
T29 DI status
[14]
T32 DI status
102
VLT
Function:
FC profile
PROFIdrive profile
ODVA
Available only with VLT
DeviceNet MCA 104 and
®
VLT
EtherNet/IP MCA
121.
CANopen DSP 402
Function:
The function corresponds to the profile
default selected in parameter 8-10 Control
Profile.
Only set if alarm 68, Safe Torque Off
occurs.
Set if a trip occurs, unless alarm 68, Safe
Torque Off is set to execute the trip.
The bit indicates the status of terminal
18.
0 indicates that the terminal is low.
1 indicates that the terminal is high.
The bit indicates the status of terminal
19.
0 indicates that the terminal is low.
1 indicates that the terminal is high.
The bit indicates the status of terminal
27.
0 indicates that the terminal is low.
1 indicates that the terminal is high.
The bit indicates the status of terminal
29.
0 indicates that the terminal is low.
1 indicates that the terminal is high.
The bit indicates the status of terminal
32.
0 indicates that the terminal is low.
Danfoss A/S © 05/2018 All rights reserved.
®
AQUA Drive FC 202
8-13 Configurable Status Word STW
This parameter enables configuration of bits 12–15 in the status
word.
Array [16]
Option:
[15]
T33 DI status
[16]
T37 DI status
®
[20]
CTW Timeout
Toggle Inverse
[21]
Thermal
warning
[30]
Brake fault
(IGBT)
[40]
Out of ref range
[60]
Comparator 0
[61]
Comparator 1
[62]
Comparator 2
[63]
Comparator 3
[64]
Comparator 4
[65]
Comparator 5
[70]
Logic Rule 0
[71]
Logic Rule 1
Function:
1 indicates that the terminal is high.
The bit indicates the status of terminal
33.
0 indicates that the terminal is low.
1 indicates that the terminal is high.
The bit indicates the status of terminal
37.
0 indicates that T37 is low (Safe Torque
Off).
1 indicates that T37 is high (normal).
The thermal warning turns on when the
temperature exceeds the limit in the
motor, frequency converter, brake
resistor, or thermistor.
Output is logic 1 when the brake IGBT is
short-circuited. Use this function to
protect the frequency converter if there
is a fault on the brake modules. Use the
output/relay to cut out the main voltage
from the frequency converter.
See parameter group 13-1* Comparators. If
comparator 0 is evaluated as true, the
output goes high. Otherwise, it is low.
See parameter group 13-1* Comparators. If
comparator 1 is evaluated as true, the
output goes high. Otherwise, it is low.
See parameter group 13-1* Comparators. If
comparator 2 is evaluated as true, the
output goes high. Otherwise, it is low.
See parameter group 13-1* Comparators. If
comparator 3 is evaluated as true, the
output goes high. Otherwise, it is low.
See parameter group 13-1* Comparators. If
comparator 4 is evaluated as true, the
output goes high. Otherwise, it is low.
See parameter group 13-1* Comparators. If
comparator 5 is evaluated as true, the
output goes high. Otherwise, it is low.
See parameter group 13-4* Logic Rules. If
logic rule 0 is evaluated as true, the
output goes high. Otherwise, it is low.
See parameter group 13-4* Logic Rules. If
logic rule 1 is evaluated as true, the
output goes high. Otherwise, it is low.
MG20OB02