Parameter Description
26-00 Terminal X42/1 Mode
Option:
3
3
[1]
Voltage
*
[2]
Pt 1000 [°C]
[3]
Pt 1000 [°F]
[4]
Ni 1000 [°C]
[5]
Ni 1000 [°F]
26-01 Terminal X42/3 Mode
Option:
218
VLT
Function:
Terminal X42/1 can be programmed as an
analog input accepting a voltage or input
from either Pt1000 (1000 Ω at 0 °C (32 °F)) or
Ni 1000 (1000 Ω at 0 °C (32 °F)) temperature
sensors. Select the mode.
° C] and [4] Ni 1000 [ ° C] if
[2] Pt 1000 [
operating in Celsius, or [3] Pt 1000 [
° F] if operating in Fahrenheit.
Ni 1000 [
NOTICE
If the input is not in use, set it for
voltage.
If set for temperature and used as feedback,
set the unit for either Celsius or Fahrenheit.
Parameter 20-12 Reference/Feedback
Unit.
Parameter 21-10 Ext. 1 Ref./Feedback
Unit.
Parameter 21-30 Ext. 2 Ref./Feedback
Unit.
Parameter 20-05 Feedback 2 Source
Unit.
Function:
Terminal X42/3 can be programmed as an
analog input accepting a voltage or input
from either Pt 1000 or Ni 1000 temperature
sensors. Select the mode.
° C] and [4] Ni 1000 [ ° C] if
[2] Pt 1000 [
operating in Celsius, or [3] Pt 1000 [
° F] if operating in Fahrenheit.
Ni 1000 [
NOTICE
If the input is not in use, set it for
voltage.
If set for temperature and used as feedback,
set the unit for either Celsius or Fahrenheit.
Parameter 20-12 Reference/Feedback
Unit.
Parameter 21-10 Ext. 1 Ref./Feedback
Unit.
Parameter 21-30 Ext. 2 Ref./Feedback
Unit.
Danfoss A/S © 05/2018 All rights reserved.
®
AQUA Drive FC 202
26-01 Terminal X42/3 Mode
Option:
[1]
Voltage
*
[2]
Pt 1000 [°C]
[3]
Pt 1000 [°F]
[4]
Ni 1000 [°C]
° F] and [5]
[5]
Ni 1000 [°F]
26-02 Terminal X42/5 Mode
Option:
[1]
Voltage
*
[2]
Pt 1000 [°C]
[3]
Pt 1000 [°F]
° F] and [5]
[4]
Ni 1000 [°C]
[5]
Ni 1000 [°F]
26-10 Terminal X42/1 Low Voltage
Range:
0.07 V
[ 0 - par.
*
6-31 V]
Function:
Parameter 20-05 Feedback 2 Source
Unit.
Function:
Terminal X42/5 can be programmed as an
analog input accepting a voltage or input
from either Pt 1000 (1000 Ω at 0 °C) or Ni
1000 (1000 Ω at 0 °C) temperature sensors.
Select the mode.
° C] and [4] Ni 1000 [ ° C] if
[2] Pt 1000 [
operating in Celsius, or [3] Pt 1000 [
° F] if operating in Fahrenheit.
Ni 1000 [
NOTICE
If the input is not in use, set it for
voltage.
If set for temperature and used as feedback,
set the unit for either Celsius or Fahrenheit:
Parameter 20-12 Reference/Feedback
Unit.
Parameter 21-10 Ext. 1 Ref./Feedback
Unit.
Parameter 21-30 Ext. 2 Ref./Feedback
Unit.
Parameter 20-05 Feedback 2 Source
Unit.
Function:
Enter the low voltage value. This analog
input scaling value should correspond to
the low reference/feedback value set in
parameter 26-14 Term. X42/1 Low Ref./Feedb.
Value.
° F] and [5]
MG20OB02