Danfoss VLT AQUA Drive FC 202 Programming Manual page 100

Software version: 3.30
Hide thumbs Also See for VLT AQUA Drive FC 202:
Table of Contents

Advertisement

Parameter Description
6-61 Terminal X30/8 Min. Scale
Range:
0 %
[0 -
*
200 %]
3
3
6-62 Terminal X30/8 Max. Scale
Range:
100
[0 -
%
200 %
*
]
6-63 Terminal X30/8 Output Bus Control
Range:
0 %
[0 - 100 %] Contains the value to apply to the output
*
6-64 Terminal X30/8 Output Timeout Preset
Range:
0 %
[0 - 100 %] Contains the value to apply to the output
*
6-70 Terminal X45/1 Output
Select the output of terminal X45/1 of VLT
MCB 113.
Option:
[0]
*
[52]
[53]
[100]
[101]
[102]
[103]
98
Function:
Scales the minimum output of the selected analog
signal on terminal X30/8. Scale the minimum
value as a percentage of the maximum signal
value. For example, enter the value 25% if the
output should be 0 mA at 25% of the maximum
output value. The value can never exceed the
corresponding setting in parameter 6-62 Terminal
X30/8 Max. Scale if the value is below 100%.
This parameter is active when VLT
Purpose I/O MCB 101 is mounted in the frequency
converter.
Function:
Scales the maximum output of the selected
analog signal on terminal X30/8. Scale the value
to the required maximum value of the current
signal output. Scale the output to give a lower
current than 20 mA at full scale, or 20 mA at an
output below 100% of the maximum signal value.
If 20 mA is the required output current at a value
between 0–100% of the full-scale output,
program the percentage value in the parameter,
that is 50%=20 mA. If a current 4–20 mA is
required at maximum output (100%), calculate
the percentage value as follows:
20 mA/desired maximum current  ×  100 %
20 mA
i . e .  10 mA:  
  ×  100 % = 200 %
10 mA
Function:
terminal when it is configured as bus-
controlled.
Function:
terminal when it is configured as bus-
controlled timeout and timeout is detected.
®
Extended Relay Card
No operation
MCO 0-20mA/0-10V
MCO 4-20mA
Output freq. 0-100
Reference Min-Max
Feedback +-200%
Motor cur. 0-Imax
Danfoss A/S © 05/2018 All rights reserved.
®
VLT
AQUA Drive FC 202
6-70 Terminal X45/1 Output
Select the output of terminal X45/1 of VLT
MCB 113.
Option:
[104]
[105]
[106]
[107]
[108]
[109]
®
General
[113]
[114]
[115]
[116]
[117]
[118]
[130]
[131]
[132]
[133]
[134]
[135]
[136]
[137]
[138]
[139]
[140]
[141]
[142]
[143]
[144]
[145]
[146]
[147]
[148]
[150]
[156]
[157]
[254]
[255]
6-71 Terminal X45/1 Min. Scale
Enter the minimum scaling value of output of the analog signal
on terminal X45/1.
Range:
0 %
*
Function:
6-72 Terminal X45/1 Max. Scale
Enter the maximum scaling value of output of the analog signal
on terminal X45/1.
Range:
100 %
*
®
Extended Relay Card
Torque 0-Tlim
Torque 0-Tnom
Power 0-Pnom
Speed 0-HighLim
Torque +-160%
Out frq 0-Fmax
Ext. Closed Loop 1
Ext. Closed Loop 2
Ext. Closed Loop 3
Cascade Reference
Shaft Power
Shaft Power 4-20mA
Out frq 0-100 4-20mA
Reference 4-20mA
Feedback 4-20mA
Motor cur. 4-20mA
Torq.0-lim 4-20 mA
Torq.0-nom 4-20mA
Power 4-20mA
Speed 4-20mA
Torque 4-20mA
Bus ctrl.
Bus ctrl. 4-20 mA
Bus ctrl t.o.
Bus ctrl t.o. 4-20mA
Ext. CL 1 4-20mA
Ext. CL 2 4-20mA
Ext. CL 3 4-20mA
Cascade Ref. 4-20mA
Main act val 0-20mA
Main act val 4-20mA
Out frq 0-Fmax 4-20mA
Flow Rate
Flow Rate 4-20mA
DC Link 0-20mA
DC Link 4-20mA
Function:
[0 - 200 %]
Function:
[0 - 200 %]
Function:
MG20OB02