Parameter Description
13-40 Logic Rule Boolean 1
Array [6]
Option:
[109] Relay 7
[110] Relay 8
3
3
[111] Relay 9
[112] System On Ref
[125] Digital input x46/1
[126] Digital input x46/3
[127] Digital input x46/5
[128] Digital input x46/7
[129] Digital input x46/9
[130] Digital input
x46/11
[131] Digital input
x46/13
[140] ATEX ETR cur.
warning
[141] ATEX ETR cur.
alarm
[142] ATEX ETR freq.
warning
[143] ATEX ETR freq.
alarm
13-41 Logic Rule Operator 1
Array [6]
Option:
[0] DISABLED
[1] AND
[2] OR
[3] AND NOT
[4] OR NOT
[5] NOT AND
[6] NOT OR
[7] NOT AND
NOT
124
VLT
Function:
Function:
Select the 1
st
logical operator to use on the
boolean inputs from parameter 13-40 Logic Rule
Boolean 1 and parameter 13-42 Logic Rule
Boolean 2.
Parameter numbers in square brackets stand
for the boolean inputs of parameters in
parameter group 13-** Smart Logic Control.
Ignores:
Parameter 13-42 Logic Rule Boolean 2.
Parameter 13-43 Logic Rule Operator 2.
Parameter 13-44 Logic Rule Boolean 3.
Evaluates the expression [13-40] AND [13-42].
Evaluates the expression [13-40] OR [13-42].
Evaluates the expression [13-40] AND NOT
[13-42].
Evaluates the expression [13-40] OR NOT
[13-42].
Evaluates the expression NOT [13-40] AND
[13-42].
Evaluates the expression NOT [13-40] OR
[13-42].
Evaluates the expression NOT [13-40] AND NOT
[13-42].
Danfoss A/S © 05/2018 All rights reserved.
®
AQUA Drive FC 202
13-41 Logic Rule Operator 1
Array [6]
Option:
[8] NOT OR
NOT
13-42 Logic Rule Boolean 2
Array [6]
Option:
[0]
False
[1]
True
[2]
Running
[3]
In range
[4]
On reference
[5]
Torque limit
[6]
Current Limit
[7]
Out of current range
[8]
Below I low
[9]
Above I high
[10]
Out of speed range
[11]
Below speed low
[12]
Above speed high
[13]
Out of feedb. range
[14]
Below feedb. low
[15]
Above feedb. high
[16]
Thermal warning
[17]
Mains out of range
[18]
Reversing
[19]
Warning
[20]
Alarm (trip)
[21]
Alarm (trip lock)
[22]
Comparator 0
[23]
Comparator 1
[24]
Comparator 2
[25]
Comparator 3
[26]
Logic rule 0
[27]
Logic rule 1
[28]
Logic rule 2
[29]
Logic rule 3
[30]
SL Time-out 0
[31]
SL Time-out 1
[32]
SL Time-out 2
[33]
Digital input DI18
[34]
Digital input DI19
[35]
Digital input DI27
[36]
Digital input DI29
[37]
Digital input DI32
Function:
Evaluates the expression NOT [13-40] OR NOT
[13-42].
Function:
nd
Select the 2
boolean (true or
false) input for the selected logic
rule.
See parameter 13-40 Logic Rule
Boolean 1 for further descriptions of
options and their functions.
MG20OB02