Parameter Description
3.12.3 RS Flip Flops
The reset/set flip flops hold the signal until set/reset.
Par. 13-15
RS-FF Operand S
Par. 13-16
RS-FF Operand R
Illustration 3.42 Reset/Set Flip Flops
2 parameters are used, and the output can be used in the
logic rules and as events.
S
R
Flip Flop Output
Illustration 3.43 Flip Flop Outputs
The 2 operators can be selected from a long list. As a
special case, the same digital input can be used as both
set and reset, making it possible to use the same digital
input as start/stop. The following settings can be used to
set up the same digital input (for example, DI32) as start/
stop.
Parameter
Parameter 13-00 SL Controller
Mode
Parameter 13-01 Start Event
Parameter 13-02 Stop Event
Parameter 13-40 Logic Rule
Boolean 1 [0]
Parameter 13-42 Logic Rule
Boolean 2 [0]
Parameter 13-41 Logic Rule
Operator 1 [0]
Parameter 13-40 Logic Rule
Boolean 1 [1]
Parameter 13-42 Logic Rule
Boolean 2 [1]
Parameter 13-41 Logic Rule
Operator 1 [1]
Parameter 13-15 RS-FF Operand
S [0]
MG20OB02
Programming Guide
Setting
Notes
On
True
False
[37] Digital
Input DI32
[2] Running –
[3] AND
NOT
[37] Digital
Input DI32
[2] Running –
[1] AND
Output from
[26] Logic
parameter 13-41 Log
rule 0
ic Rule Operator 1
[0].
Danfoss A/S © 05/2018 All rights reserved.
Parameter
Setting
Parameter 13-16 RS-FF Operand
[27] Logic
R [0]
rule 1
Parameter 13-51 SL Controller
[94] RS
Event [0]
Flipflop 0
Parameter 13-52 SL Controller
[22] Run
Action [0]
Parameter 13-51 SL Controller
[27] Logic
Event [1]
rule 1
Parameter 13-52 SL Controller
[24] Stop
Action [1]
Table 3.21 Operators
13-15 RS-FF Operand S
Array [8]
Select the set input.
Option:
[0]
False
[1]
True
[2]
Running
[3]
In range
[4]
On reference
[5]
Torque limit
[6]
Current Limit
[7]
Out of current range
[8]
Below I low
[9]
Above I high
[10]
Out of speed range
[11]
Below speed low
[12]
Above speed high
[13]
Out of feedb. range
[14]
Below feedb. low
[15]
Above feedb. high
[16]
Thermal warning
[17]
Mains out of range
[18]
Reversing
[19]
Warning
[20]
Alarm (trip)
[21]
Alarm (trip lock)
[22]
Comparator 0
[23]
Comparator 1
[24]
Comparator 2
[25]
Comparator 3
[26]
Logic rule 0
[27]
Logic rule 1
[28]
Logic rule 2
[29]
Logic rule 3
[30]
SL Time-out 0
Notes
Output from
parameter 13-41 Log
ic Rule Operator 1
[1].
3
Output from
parameter 13-15 RS-
FF Operand S and
parameter 13-16 RS-
FF Operand R.
Function:
119
3