Danfoss VLT AQUA Drive FC 202 Programming Manual page 221

Software version: 3.30
Hide thumbs Also See for VLT AQUA Drive FC 202:
Table of Contents

Advertisement

Parameter Description
26-11 Terminal X42/1 High Voltage
Range:
Function:
10 V
[ par. 6-30
Enter the high-voltage value. This analog
*
- 10 V]
input scaling value should correspond to the
high reference/feedback value set in
parameter 26-15 Term. X42/1 High Ref./Feedb.
Value.
26-14 Term. X42/1 Low Ref./Feedb. Value
Range:
0 ReferenceFeed-
[-999999.999 -
backUnit
999999.999
*
ReferenceFeed-
backUnit]
26-15 Term. X42/1 High Ref./Feedb. Value
Range:
100 Reference-
[-999999.999 -
FeedbackUnit
999999.999
*
ReferenceFeed-
backUnit]
26-16 Term. X42/1 Filter Time Constant
Range:
Function:
NOTICE
0.005 s
[0.005 - 10
*
s]
This parameter cannot be adjusted
while the motor is running.
This is a first-order digital low-pass filter
time constant for suppressing noise in
terminal X42/1. A high time constant
value improves dampening, but also
increases the time delay through the
filter.
26-17 Term. X42/1 Live Zero
Option:
Function:
This parameter makes it possible to enable the
live zero monitoring, for example, where the
analog input is the frequency converter control,
rather than being used as a decentral I/O system,
such as a building management system.
[0]
Disabled
[1]
Enabled
*
26-20 Terminal X42/3 Low Voltage
Range:
Function:
0.07 V
[ 0 - par.
Enter the low voltage value. This analog
*
6-31 V]
input scaling value should correspond to
the low reference/feedback value set in
MG20OB02
Programming Guide
Function:
Enter the analog input
scaling value that
corresponds to the low-
voltage value set in
parameter 26-10 Terminal
X42/1 Low Voltage.
Function:
Enter the analog input
scaling value that
corresponds to the high-
voltage value set in
parameter 26-11 Terminal
X42/1 High Voltage.
Danfoss A/S © 05/2018 All rights reserved.
26-20 Terminal X42/3 Low Voltage
Range:
Function:
parameter 26-24 Term. X42/3 Low Ref./Feedb.
Value.
26-21 Terminal X42/3 High Voltage
Range:
Function:
10 V
[ par. 6-30
Enter the high-voltage value. This analog
*
- 10 V]
input scaling value should correspond to the
high reference/feedback value set in
parameter 26-25 Term. X42/3 High Ref./Feedb.
Value.
26-24 Term. X42/3 Low Ref./Feedb. Value
Range:
0 ReferenceFeed-
[-999999.999 -
backUnit
999999.999
*
ReferenceFeed-
backUnit]
26-25 Term. X42/3 High Ref./Feedb. Value
Range:
100 Reference-
[-999999.999 -
FeedbackUnit
999999.999
*
ReferenceFeed-
backUnit]
26-26 Term. X42/3 Filter Time Constant
Range:
Function:
NOTICE
0.005 s
[0.005 - 10
*
s]
This parameter cannot be adjusted
while the motor is running.
Enter the time constant. This is a first-
order digital low-pass filter time constant
for suppressing noise in terminal X42/3. A
high time constant value improves
dampening, but also increases the time
delay through the filter.
26-27 Term. X42/3 Live Zero
Option:
Function:
This parameter makes it possible to enable the
live zero monitoring, for example, where the
analog input is the frequency converter control,
rather than being used as a decentral I/O system,
such as a building management system.
[0]
Disabled
[1]
Enabled
*
Function:
Enter the analog input
scaling value that
corresponds to the low-
voltage value set in
parameter 26-20 Terminal
X42/3 Low Voltage.
Function:
Enter the analog input
scaling value that
corresponds to the high-
voltage value set in
parameter 26-21 Terminal
X42/3 High Voltage.
219