Parameter Description
3-16 Reference 2 Source
Option:
3
3
[0]
No function
*
[1]
Analog Input
53
[2]
Analog Input
54
[7]
Pulse input 29
[8]
Pulse input 33
[20] Digital
pot.meter
[21] Analog input
X30/11
[22] Analog input
X30/12
[23] Analog Input
X42/1
[24] Analog Input
X42/3
[25] Analog Input
X42/5
[29] Analog Input
X48/2
[30] Ext. Closed
Loop 1
[31] Ext. Closed
Loop 2
[32] Ext. Closed
Loop 3
[33] PCD Bus
Reference
[35] Digital input
select
68
®
VLT
AQUA Drive FC 202
Function:
NOTICE
This parameter cannot be adjusted
while the motor is running.
Select the reference input to be used for
nd
the 2
reference signal:
Parameter 3-15 Reference 1 Source.
Parameter 3-16 Reference 2 Source.
Parameter 3-17 Reference 3 Source.
Define up to 3 different reference signals.
The sum of these reference signals defines
the actual reference.
The frequency converter selects AI53 or
AI54 as the reference source based on the
input signal defined in option [42] Ref
source bit 0 as 1 of the digital inputs. For
more information, see parameter group 5-1*
Digital Inputs, option [42] Ref source bit 0.
Danfoss A/S © 05/2018 All rights reserved.
3-17 Reference 3 Source
Option:
Function:
NOTICE
This parameter cannot be adjusted
while the motor is running.
Select the reference input to be used for
rd
the 3
reference signal:
Parameter 3-15 Reference 1 Source.
Parameter 3-16 Reference 2 Source.
Parameter 3-17 Reference 3 Source.
Define up to 3 different reference signals.
The sum of these reference signals defines
the actual reference.
[0]
No function
*
[1]
Analog Input
53
[2]
Analog Input
54
[7]
Pulse input 29
[8]
Pulse input 33
[20] Digital
pot.meter
[21] Analog input
X30/11
[22] Analog input
X30/12
[23] Analog Input
X42/1
[24] Analog Input
X42/3
[25] Analog Input
X42/5
[29] Analog Input
X48/2
[30] Ext. Closed
Loop 1
[31] Ext. Closed
Loop 2
[32] Ext. Closed
Loop 3
[33] PCD Bus
Reference
[35] Digital input
The frequency converter selects AI53 or
select
AI54 as the reference source based on the
input signal defined in option [42] Ref
source bit 0 as 1 of the digital inputs. For
more information, see parameter group 5-1*
Digital Inputs, option [42] Ref source bit 0.
MG20OB02