Parameter Description
24-06 Emergency Mode Reference Source
Option:
Function:
Select the external reference input to
be used for the emergency mode.
This signal is added to the value set
in parameter 24-06 Emergency Mode
Reference Source.
[0]
No function
*
[1]
Analog Input 53
[2]
Analog Input 54
[7]
Pulse input 29
[8]
Pulse input 33
[20] Digital pot.meter
[21] Analog input X30/11
[22] Analog input X30/12
[23] Analog Input X42/1
[24] Analog Input X42/3
[25] Analog Input X42/5
[29] Analog Input X48/2
[33] PCD Bus Reference
24-07 Emergency Mode Feedback Source
Option:
Function:
Select the feedback input to be used
for the emergency mode feedback
signal when emergency mode is
active.
If the motor is also controlled by the
built–in PID controller when in
normal operation, the same
transmitter can be used for both
cases by selecting the same source.
[0]
No function
*
[1]
Analog Input 53
[2]
Analog Input 54
[3]
Pulse input 29
[4]
Pulse input 33
[7]
Analog Input X30/11
[8]
Analog Input X30/12
[9]
Analog Input X42/1
[10]
Analog Input X42/3
[11]
Analog Input X42/5
[99]
Normal Feedback
[100] Bus Feedback 1
[101] Bus Feedback 2
[102] Bus feedback 3
MG20OB02
Programming Guide
24-09 Emergency Mode Alarm Handling
Option:
[0]
Trip+Reset,
Critical
Alarms
[1]
Trip, Critical
*
Alarms
[2]
Trip, All
Alarms/Test
NOTICE
Certain alarms are warranty-affecting alarms that can
affect the lifetime of the frequency converter. Should 1
of these ignored alarms occur while in emergency mode,
a log of the event is stored in the emergency mode log.
Here the 10 latest events of warranty-affecting alarms,
emergency mode activation, and emergency mode
deactivation are stored.
NOTICE
The setting in parameter 14-20 Reset Mode is disregarded
if emergency mode is active (see parameter group 24-0*
Emergency Mode).
Num-
ber
4
7
8
9
13
14
16
29
33
38
65
68
Table 3.33 Emergency Mode Alarm Handling
Danfoss A/S © 05/2018 All rights reserved.
Function:
If this mode is selected, the frequency
converter continues to run, ignoring most
alarms, even if doing so may result in
damage of the frequency converter. Critical
alarms are alarms which cannot be
suppressed, but a restart attempt is possible
(infinity automatic reset).
If there is a critical alarm, the frequency
converter trips and does not auto restart
(manual reset).
It is possible to test the operation of
emergency mode, but all alarm states are
activated normally (manual reset).
Critical
Description
alarms
Mains ph. Loss
DC overvolt
x
DC undervolt
x
Inverter overloaded
Over current
x
Earth (ground) fault
x
Short circuit
x
Power card temp
Inrush fault
Internal fault
Ctrl. card temp
Safe Stop
x
3
3
Warranty-
affecting
alarms
x
x
x
x
x
x
205