Danfoss VLT AQUA Drive FC 202 Programming Manual page 14

Software version: 3.30
Hide thumbs Also See for VLT AQUA Drive FC 202:
Table of Contents

Advertisement

Introduction
1
1
1.9.3 Pulse Start/Stop
Terminal 18 = Parameter 5-10 Terminal 18 Digital Input [9]
Latched start.
Terminal 27 = Parameter 5-12 Terminal 27 Digital Input [6]
Stop inverse.
Terminal 37 = Safe Torque Off (where available).
12
13
18
Start
Speed
Start (18)
Start (27)
Illustration 1.7 Pulse Start/Stop
1.9.4 Speed Up/Down
Terminals 29/32 = Speed up/down
Terminal 18 = Parameter 5-10 Terminal 18 Digital Input [9]
Start (default).
Terminal 27 = Parameter 5-12 Terminal 27 Digital Input [19]
Freeze reference.
Terminal 29 = Parameter 5-13 Terminal 29 Digital Input [21]
Speed up.
Terminal 32 = Parameter 5-14 Terminal 32 Digital Input [22]
Speed down.
12
VLT
19
27
29
32
33
20
37
Stop inverse
Safe Stop
Danfoss A/S © 05/2018 All rights reserved.
®
AQUA Drive FC 202
Illustration 1.8 Speed Up/Down
1.9.5 Potentiometer Reference
Voltage reference via a potentiometer
Reference source 1 = [1] Analog input 53 (default).
Terminal 53, Low Voltage = 0 V.
Terminal 53, High Voltage = 10 V.
Terminal 53, Low Ref./Feedback = 0 RPM.
Terminal 53, High Ref./Feedback = 1500 RPM.
Switch S201 = OFF (U).
Illustration 1.9 Potentiometer Reference
12
18
27
29
32
37
Speed RPM
39 42
P 6-15
Ref. voltage
P 6-11 10V
1 k
+24V
Par. 5-10
Par. 5-12
Par. 5-13
Par. 5-14
50
53 54
55
MG20OB02

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents