Parameter Description
23-15 Reset Maintenance Word
Option:
3
3
[0]
Do not
*
reset
[1]
Do
reset
23-16 Maintenance Text
Array [6]
Range:
0
[0 -
*
20 ]
3.20.3 23-5* Energy Log
The frequency converter is continuously accumulating the
consumption of the motor controlled, based on the actual
power yielded by the frequency converter.
This data can be used for an energy log function allowing
to compare and structure the information about the
energy consumption related to time.
There are 2 functions:
Data related to a pre-programmed period,
defined by a set date and time for start.
Data related to a predefined period back in time,
for example last 7 days within the pre-
programmed period.
For each of the above 2 functions, the data is stored in
several counters allowing for selecting time frame and a
split on hours, days, or weeks.
The period/split (resolution) can be set in
parameter 23-50 Energy Log Resolution.
196
Function:
NOTICE
When messages are reset, maintenance
item, action, and maintenance date/time
are not canceled.
Parameter 23-12 Maintenance Time Base is
set to [0] Disabled.
Set this parameter to [1] Do reset to reset the
maintenance word in parameter 16-96 Maintenance
Word and reset the message shown in the LCP.
This parameter changes back to [0] Do not reset
when pressing [OK].
Function:
6 individual texts (Maintenance Text
0...Maintenance Text 5) can be written for use in
either parameter 23-10 Maintenance Item or
parameter 23-11 Maintenance Action.
The text is written according to the guidelines in
parameter 0-37 Display Text 1.
Danfoss A/S © 05/2018 All rights reserved.
®
VLT
AQUA Drive FC 202
The data is based on the value registered by the kWh
counter in the frequency converter. This counter value can
be read in parameter 15-02 kWh Counter containing the
accumulated value since the first power-up or latest reset
of the counter (parameter 15-06 Reset kWh Counter).
All data for the energy log is stored in counters, which can
be read from parameter 23-53 Energy Log.
Counter 6
Counter 5
Counter 4
Counter 3
Counter 2
Counter 1
Counter 0
Illustration 3.75 Energy Log Graph
Counter 00 always contains the oldest data. A counter
covers a period from XX:00 to XX:59 if hours or 00:00 to
23:59 if days.
If logging either the last hours or last days, the counters
shift contents at XX:00 every hour or at 00:00 every day.
The counter with highest index is always subject to update
(containing data for the actual hour since XX:00 or the
actual day since 00:00).
The contents of counters can be shown as bars on the LCP.
Select Quick Menu, Loggings, Energy Log: Trending Continued
Bin/Trending Timed Bin/Trending Comparison.
23-50 Energy Log Resolution
Option:
Σ kWh
(P 15-02, kWh Counter)
Function:
NOTICE
The frequency converter has no back-
up of the clock function. The set date/
time resets to default (2000-01-01
00:00) after a power-down unless a
real-time clock-module with back-up is
installed. Therefore, the logging is
stopped until date/time is readjusted
in parameter 0-70 Date and Time. In
parameter 0-79 Clock Fault, it is
possible to program a warning if the
clock has not been set properly, for
example after a power-down.
Select the type of period for logging
consumption: [0] Hour of Day, [1] Day of
Days