Parameter Description
13-20 SL Controller Timer
Array [8]
Range:
Size
related
0 ]
*
3
3
3.12.5 13-4* Logic Rules
Combine up to 3 boolean inputs (true/false inputs) from
timers, comparators, digital inputs, status bits, and events
using the logical operators AND, OR, and NOT. Select
boolean inputs for the calculation in parameter 13-40 Logic
Rule Boolean 1, parameter 13-42 Logic Rule Boolean 2, and
parameter 13-44 Logic Rule Boolean 3. Define the operators
used to logically combine the selected inputs in
parameter 13-41 Logic Rule Operator 1 and
parameter 13-43 Logic Rule Operator 2.
Par. 13-40
Logic Rule Boolean 1
Par. 13-42
Logic Rule Boolean 2
Illustration 3.44 Logic Rules
Priority of calculation
The results of parameter 13-40 Logic Rule Boolean 1,
parameter 13-41 Logic Rule Operator 1, and
parameter 13-42 Logic Rule Boolean 2 are calculated first.
The outcome (true/false) of this calculation is combined
with the settings of parameter 13-43 Logic Rule Operator 2
and parameter 13-44 Logic Rule Boolean 3, yielding the final
result (true/false) of the logic rule.
13-40 Logic Rule Boolean 1
Array [6]
Option:
[0]
False
[1]
True
[2]
Running
[3]
In range
122
Function:
[ 0 -
Enter the value to define the duration of
the false output from the programmed
timer. A timer is only false if it is started
by an action (for example [29] Start timer
1) and until the given timer value has
elapsed.
Par. 13-41
Par. 13-43
Logic Rule Operator 1
Logic Rule Operator 2
. . .
. . .
. . .
. . .
Par. 13-44
Logic Rule Boolean 3
Function:
Enters the fixed value of false in the
logic rule.
Enters the fixed value of true in the
logic rule.
See parameter group 5-3* Digital
Outputs for further description.
See parameter group 5-3* Digital
Outputs for further description.
Danfoss A/S © 05/2018 All rights reserved.
®
VLT
AQUA Drive FC 202
13-40 Logic Rule Boolean 1
Array [6]
Option:
[4]
On reference
[5]
Torque limit
[6]
Current Limit
[7]
Out of current
range
[8]
Below I low
[9]
Above I high
[10]
Out of speed
range
[11]
Below speed low
[12]
Above speed high See parameter group 5-3* Digital
[13]
Out of feedb.
range
[14]
Below feedb. low
[15]
Above feedb. high See parameter group 5-3* Digital
[16]
Thermal warning
[17]
Mains out of
range
[18]
Reversing
[19]
Warning
[20]
Alarm (trip)
[21]
Alarm (trip lock)
[22]
Comparator 0
[23]
Comparator 1
[24]
Comparator 2
[25]
Comparator 3
Function:
See parameter group 5-3* Digital
Outputs for further description.
See parameter group 5-3* Digital
Outputs for further description.
See parameter group 5-3* Digital
Outputs for further description.
See parameter group 5-3* Digital
Outputs for further description.
See parameter group 5-3* Digital
Outputs for further description.
See parameter group 5-3* Digital
Outputs for further description.
See parameter group 5-3* Digital
Outputs for further description.
Outputs for further description.
See parameter group 5-3* Digital
Outputs for further description.
See parameter group 5-3* Digital
Outputs for further description.
Outputs for further description.
See parameter group 5-3* Digital
Outputs for further description.
See parameter group 5-3* Digital
Outputs for further description.
See parameter group 5-3* Digital
Outputs for further description.
See parameter group 5-3* Digital
Outputs for further description.
See parameter group 5-3* Digital
Outputs for further description.
See parameter group 5-3* Digital
Outputs for further description.
Use the result of comparator 0 in the
logic rule.
Use the result of comparator 1 in the
logic rule.
Use the result of comparator 2 in the
logic rule.
Use the result of comparator 3 in the
logic rule.
MG20OB02