Parameter Description
4-16 Torque Limit Motor Mode
Range:
Function:
Size
[ 0 -
Enter the maximum torque limit for motor
related
1000.0 %
operation. The torque limit is active in the
*
]
speed range up to and including the
nominal motor speed set in
parameter 1-25 Motor Nominal Speed. To
protect the motor from reaching the
stalling torque, the default setting is 1.1 x
the rated motor torque (calculated value).
See also parameter 14-25 Trip Delay at
Torque Limit for further details.
If a setting in parameter 1-00 Configuration
Mode to parameter 1-28 Motor Rotation
Check is changed, parameter 4-16 Torque
Limit Motor Mode is not automatically reset
to the default setting.
4-17 Torque Limit Generator Mode
Range:
Function:
100
[ 0 -
Enter the maximum torque limit for generator-
%
1000.0 %
mode operation. The torque limit is active in
*
]
the speed range up to and including the
nominal motor speed (parameter 1-25 Motor
Nominal Speed). Refer to parameter 14-25 Trip
Delay at Torque Limit for further details.
If a setting in parameter 1-00 Configuration
Mode to parameter 1-28 Motor Rotation Check is
changed, parameter 4-17 Torque Limit Generator
Mode is not automatically reset to the default
settings.
4-18 Current Limit
Range:
Function:
160.0
[1.0 -
Enter the current limit for motor and
%
1000.0 %
generator operation. To protect the motor
*
]
from reaching the stalling torque, the default
setting is 1.1 x the rated motor torque
(calculated value). If a setting in
parameter 1-00 Configuration Mode to
parameter 1-26 Motor Cont. Rated Torque is
changed, parameter 4-18 Current Limit is not
automatically reset to the default setting.
4-19 Max Output Frequency
Range:
Function:
NOTICE
Size
[ 1 -
related
590
*
This parameter cannot be adjusted
Hz]
while the motor is running.
NOTICE
When parameter 1-10 Motor Construction
is set to [1] PM, non-salient SPM, the
maximum value is limited to 300 Hz.
MG20OB02
Programming Guide
4-19 Max Output Frequency
Range:
3.6.2 4-5* Adj. Warnings
Define adjustable warning limits for current, speed,
reference, and feedback.
NOTICE
Not visible in the display, only in MCT 10 Set-up
Software.
4-50 Warning Current Low
Range:
0
[ 0 -
A
par.
*
4-51
A]
4-51 Warning Current High
Range:
Size
related
*
Danfoss A/S © 05/2018 All rights reserved.
Function:
Enter the maximum output frequency value.
Parameter 4-19 Max Output Frequency specifies
the absolute limit on the frequency converter
output frequency for improved safety in
applications where unintended overspeeding
must be avoided. This absolute limit applies to
all configurations and is independent of the
setting in parameter 1-00 Configuration Mode.
Function:
Warnings are shown on the display, programmed
output, or fieldbus.
I
motor
I
ON REF
LIM
(P 4-18)
I
HIGH
(P 4-51)
IN RANGE
I
LOW
(P 4-50)
n
n
n
REF
MIN
LOW
HIGH
(P 4-11)
(P 4-52)
(P 4-53)
Illustration 3.27 Low Current Limit
Enter the I
value. When the motor current drops
LOW
below this limit (I
), the display reads Current low.
LOW
The signal outputs can be programmed to produce
a status signal on terminal 27 or 29, and on relay
output 01 or 02. Refer to Illustration 3.27.
Function:
[ par.
Enter the I
value. When the motor
HIGH
4-50 - par.
current exceeds this limit (I
16-37 A]
display reads Current high. The signal
outputs can be programmed to produce
a status signal on terminal 27 or 29, and
on relay output 01 or 02. Refer to
Illustration 3.27.
3
n
[RPM]
motor
n
MAX
(P 4-13)
), the
HIGH
73
3