Danfoss VLT AQUA Drive FC 202 Programming Manual page 144

Software version: 3.30
Hide thumbs Also See for VLT AQUA Drive FC 202:
Table of Contents

Advertisement

Parameter Description
15-10 Logging Source
Array [4]
Option:
[1632]
Brake Energy /s
[1633]
Brake Energy /2 min
3
3
[1634]
Heatsink Temp.
[1635]
Inverter Thermal
[1650]
External Reference
[1651]
Pulse Reference
[1652]
Feedback [Unit]
[1660]
Digital Input
[1662]
Analog Input 53
[1664]
Analog Input 54
[1665]
Analog Output 42 [mA]
[1666]
Digital Output [bin]
[1675]
Analog In X30/11
[1676]
Analog In X30/12
[1677]
Analog Out X30/8 [mA]
[1690]
Alarm Word
[1692]
Warning Word
[1694]
Ext. Status Word
[3470]
MCO Alarm Word 1
[3471]
MCO Alarm Word 2
15-11 Logging Interval
Array [4]
Range:
Size related
*
15-12 Trigger Event
Option:
[0]
False
*
[1]
True
[2]
Running
[3]
In range
[4]
On reference
[5]
Torque limit
[6]
Current Limit
[7]
Out of current range
[8]
Below I low
[9]
Above I high
[10] Out of speed range
[11] Below speed low
[12] Above speed high
[13] Out of feedb. range
142
Function:
[ 0 - 0 ] Enter the interval in ms between each
sampling of the variables to be logged.
Function:
Selects the trigger event. When the
trigger event occurs, a window is
applied to freeze the log. The log
then retains a specified percentage of
samples before the occurrence of the
trigger event
(parameter 15-14 Samples Before
Trigger).
Danfoss A/S © 05/2018 All rights reserved.
®
VLT
AQUA Drive FC 202
15-12 Trigger Event
Option:
Function:
[14] Below feedb. low
[15] Above feedb. high
[16] Thermal warning
[17] Mains out of range
[18] Reversing
[19] Warning
[20] Alarm (trip)
[21] Alarm (trip lock)
[22] Comparator 0
[23] Comparator 1
[24] Comparator 2
[25] Comparator 3
[26] Logic rule 0
[27] Logic rule 1
[28] Logic rule 2
[29] Logic rule 3
[33] Digital input DI18
[34] Digital input DI19
[35] Digital input DI27
[36] Digital input DI29
[37] Digital input DI32
[38] Digital input DI33
[50] Comparator 4
[51] Comparator 5
[60] Logic rule 4
[61] Logic rule 5
15-13 Logging Mode
Option:
[0]
Log always
*
[1]
Log once
on trigger
15-14 Samples Before Trigger
Range:
50
[0 - 100 ] Enter the percentage of all samples to be
*
Function:
Function:
Select [0] Log always for continuous logging.
Select [1] Log once on trigger to start and stop
logging conditionally using
parameter 15-12 Trigger Event and
parameter 15-14 Samples Before Trigger.
Function:
retained in the log before a trigger event occurs.
See also parameter 15-12 Trigger Event and
parameter 15-13 Logging Mode.
MG20OB02

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents