Advertisement

Parameter Description
5-54 Pulse Filter Time Constant #29
Range:
Function:
NOTICE
100
[5 -
ms
1000 ms]
*
This parameter cannot be adjusted
while the motor is running.
Enter the pulse filter time constant. The
pulse filter dampens oscillations of the
feedback signal, which is an advantage if
there is a lot of noise in the system. A high
time constant value results in better
dampening, but also increases the time
delay through the filter.
5-55 Term. 33 Low Frequency
Range:
Function:
100 Hz
[0 - 110000
Enter the low frequency corresponding
*
Hz]
to the low motor shaft speed (that is
low reference value) in
parameter 5-57 Term. 33 Low Ref./Feedb.
Value.
5-56 Term. 33 High Frequency
Range:
Function:
100 Hz
[0 - 110000
Enter the high frequency corresponding
*
Hz]
to the high motor shaft speed (that is
high reference value) in
parameter 5-58 Term. 33 High Ref./Feedb.
Value.
5-57 Term. 33 Low Ref./Feedb. Value
Range:
0 ReferenceFeed-
[-999999.999 -
backUnit
999999.999
*
ReferenceFeed-
backUnit]
5-58 Term. 33 High Ref./Feedb. Value
Range:
100 Reference-
[-999999.999 -
FeedbackUnit
999999.999
*
ReferenceFeed-
backUnit]
5-59 Pulse Filter Time Constant #33
Range:
Function:
NOTICE
100
[5 - 1000
ms
ms]
*
This parameter cannot be adjusted
while the motor is running.
MG20OB02
Programming Guide
3.7.6 5-6* Pulse Outputs
Parameters for configuring the scaling and output
functions of pulse outputs. The pulse outputs are
designated to terminal 27 or 29. Select terminal 27 output
in parameter 5-01 Terminal 27 Mode and terminal 29 output
in parameter 5-02 Terminal 29 Mode.
Function:
Enter the low reference
value [RPM] for the motor
shaft speed. This is also
the low feedback value,
see also
parameter 5-52 Term. 29
Low Ref./Feedb. Value.
Function:
Enter the high reference
value [RPM] for the motor
shaft speed. See also
parameter 5-53 Term. 29
High Ref./Feedb. Value.
Danfoss A/S © 05/2018 All rights reserved.
5-59 Pulse Filter Time Constant #33
Range:
Function:
Enter the pulse filter time constant. The
low-pass filter reduces the influence and
dampens oscillations on the feedback
signal from the control.
This is an advantage if there is a lot of
noise in the system.
Output value
High output
value
P 5-60(term27)
P 5-63(term29)
Illustration 3.32 Pulse Output
5-60 Terminal 27 Pulse Output Variable
Range:
Function:
NOTICE
This parameter cannot be
adjusted while the motor is
running.
[0]
No operation
Select the operation variable assigned
*
for terminal 27 readouts.
[45]
Bus ctrl.
[48]
Bus ctrl., timeout
[51]
MCO controlled
[100] Output frequency
[101] Reference
[102] Feedback
[103] Motor current
[104] Torque rel to limit
[105] Torq relate to rated
[106] Power
[107] Speed
High freq.
Output
P 5-62(term27)
(Hz)
P 5-65(term29)
87