Parameter Description
Off delay timer=10 s. The nominal power must be
below 10% for 10 s to disconnect the capacitors.
If the nominal power exceeds 10% during the 10
s delay, the timer (10 s) restarts.
The capacitor reconnect delay (default=25 s with
a range 1–120 s, see parameter 5-80 AHF Cap
Reconnect Delay) is used for the minimum off-
time for the AHF capacitor output function.
If there is a power loss, the frequency converter
guarantees that the minimum off-time is
respected when power is restored.
100%
90%
80%
70%
60%
50%
40%
30%
....................................................................................................................................................................................................................
....................................................................................................................................................................................................................
20%
10%
...................................................................................................................................................................................................................
0%
On
10
20
30
40 50 60
Time (s)
Illustration 3.33 Example of the Output Function
t
shows the off delay timer (10 s).
1
t
shows the capacitor reconnect delay (parameter 5-80 AHF
2
Cap Reconnect Delay).
When the nominal power of the frequency converter
exceeds 20%, the output function turns on. When the
power goes below 10%, an off delay timer has to expire
before the output goes low. This is represented by t
the output goes low, the capacitor reconnect delay timer
has to expire before the output is allowed to be on again,
shown by t
. When t
expires, the nominal power is above
2
2
30% and the relay does not turn on.
3.7.7 5-9* Bus-controlled
This parameter group selects digital and relay outputs via a
fieldbus setting.
MG20OB02
Programming Guide
t
t
1
2
70
80
90 100 110 120 130
. After
1
Danfoss A/S © 05/2018 All rights reserved.
5-90 Digital & Relay Bus Control
Range:
Function:
0
[0 -
This parameter holds the state of the digital
*
2147483647 ]
outputs and relays that are controlled by
bus.
A logical 1 indicates that the output is high
or active.
A logical 0 indicates that the output is low
or inactive.
Bit 0
CC digital output, terminal 27
Bit 1
CC digital output, terminal 29
Bit 2
GPIO digital output, terminal X
30/6
Bit 3
GPIO digital output, terminal X
30/7
Bit 4
CC relay 1 output terminal
Bit 5
CC relay 2 output terminal
Bit 6
Option B relay 1 output terminal
Bit 7
Option B relay 2 output terminal
Bit 8
Option B relay 3 output terminal
Bit 9–
Reserved for future terminals
15
Bit 16
Option C relay 1 output terminal
Bit 17
Option C relay 2 output terminal
Bit 18
Option C relay 3 output terminal
Bit 19
Option C relay 4 output terminal
Bit 20
Option C relay 5 output terminal
Bit 21
Option C relay 6 output terminal
Bit 22
Option C relay 7 output terminal
Bit 23
Option C relay 8 output terminal
Bit 24–
Reserved for future terminals
31
Table 3.16 Digital Output Bits
5-93 Pulse Out #27 Bus Control
Range:
Function:
0 %
[0 - 100 %] Contains the frequency to apply to the
*
digital output terminal 27 when it is
configured as bus-controlled.
5-94 Pulse Out #27 Timeout Preset
Range:
Function:
0 %
[0 - 100 %] Contains the frequency to apply to the
*
digital output terminal 27 when it is
configured as bus-controlled timeout, and
timeout is detected.
5-95 Pulse Out #29 Bus Control
Range:
Function:
0 %
[0 - 100 %] Contains the frequency to apply to the
*
digital output terminal 29 when it is
configured as bus-controlled.
3
3
89