Parameters: 16-** Data Readouts - Danfoss VLT AutomationDrive FC 301 Programming Manual

Hide thumbs Also See for VLT AutomationDrive FC 301:
Table of Contents

Advertisement

Parameter Descriptions

3.17 Parameters: 16-** Data Readouts

3.17.1 16-0* General Status
16-00 Control Word
Range:
Function:
0
[0 - 65535 ] View the control word sent from the frequency
*
converter via the serial communication port in
hex code.
16-01 Reference [Unit]
Range:
0 ReferenceFeed-
[-999999 -
backUnit
999999
*
ReferenceFeed-
backUnit]
16-02 Reference [%]
Range:
Function:
0 %
[-200 -
View the total reference. The total reference
*
200 %]
is the sum of digital, analog, preset, bus,
and freeze references, plus catch up and
slow down.
16-03 Status Word
Range:
Function:
0
[0 - 65535 ] View the status word sent from the frequency
*
converter via the serial communication port in
hex code.
16-05 Main Actual Value [%]
Range:
Function:
0 %
[-100 - 100 %] View the 2-byte word sent with the status
*
word to the fieldbus master reporting the
main actual value.
16-06 Actual Position
Range:
0 CustomRea-
[-2000000000
doutUnit2
- 2000000000
*
CustomRea-
doutUnit2]
MG33ML02
Programming Guide
Function:
View the present reference
value applied on impulse or
analog basis in the unit
resulting from the configu-
ration selected in
parameter 1-00 Configu-
ration Mode (Hz, Nm, or
RPM).
Function:
Shows the actual position in
position units defined in
parameter group 17-7* Position
Scaling. The value is based on
the encoder feedback in closed
loop or on the angle calculated
by the motor control in open
loop. For information about
configuring the readouts, see
chapter 3.18.5 17-7* Position
Scaling.
Danfoss A/S © 02/2016 All rights reserved.
16-07 Target Position
Shows the actual end target position for the active positioning
command in position units. Position units are defined in
parameter group 17-7* Position Scaling.
Range:
0 CustomRea-
[-2000000000 -
doutUnit2
2000000000
*
CustomReadoutUnit2]
16-08 Position Error
Shows the actual position error in position units defined in
parameter group 17-7* Position Scaling. Position error is the
difference between the actual position and the commanded
position. The position error is the input for the position PI
controller.
Range:
0 CustomRea-
[-2000000000 -
doutUnit2
2000000000
*
CustomReadoutUnit2]
16-09 Custom Readout
Range:
0 CustomRea-
[0 - 999999.99
doutUnit
CustomRea-
*
doutUnit]
3.17.2 16-1* Motor Status
16-10 Power [kW]
Range:
Function:
0 kW
[0 -
Shows motor power in kW. The value shown is
*
10000
calculated based on the actual motor voltage
kW]
and motor current. The value is filtered, and
therefore approximately 1.3 s may pass from
when an input value changes to when the
data readout values change. The resolution of
readout value on fieldbus is in 10 W steps.
16-11 Power [hp]
Range:
Function:
0 hp
[0 -
View the motor power in hp. The value
*
10000 hp]
shown is calculated based on the actual
motor voltage and motor current. The value is
filtered, and therefore approximately 1.3 ms
may pass from when an input value changes
to when the data readout values change.
16-12 Motor Voltage
Range:
Function:
0 V
[0 - 6000 V] View the motor voltage, a calculated value
*
used for controlling the motor.
Function:
Function:
Function:
View the value of custom
readout from
parameter 0-30 Unit for User-
defined Readout to
parameter 0-32 Custom Readout
Max Value.
173
3
3

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vlt automationdrive fc 302

Table of Contents