Allen-Bradley Kinetix 6200 User Manual page 309

Modular multi-axis servo drives
Hide thumbs Also See for Kinetix 6200:
Table of Contents

Advertisement

In this example, the Message Configuration (MSG) instruction is set to
read the digital input assignments of your control module.
a. From the Message Type pull-down menu, choose sercos IDN Read.
b. From the Identification Number pull-down menus, choose P-0-052.
This example is for reading the assignment for IOD-41 (Enable is the
default setting, 1 is the Enable IDN value). Refer to
page 69
for other digital input IDN assignments and values.
3. Click New Tag.
4. The New Tag dialog box opens.
5. Type the name of your Destination tag.
In this example, the tag name is Read_Value.
6. Click OK.
In this example, the MSG instruction reads the P-0-052 IDN value,
which is tied to digital input 1 (IOD-41), and places it in the destination
as specified by the new tag.
7. Click the Communication tab.
Rockwell Automation Publication 2094-UM002G-EN-P - August 2016
Changing the Default IDN Parameter Values
Digital Inputs
Appendix F
on
309

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents