IP addresses
3.2 IPv4 address
Outside the local area network, the distinction between network ID and host ID is of no
significance, in this case packets are delivered based on the entire IP address.
Note
In the bit representation of the subnet mask, the "ones" must be set left-justified; in other words,
there must be no "zeros" between the "ones".
3.2.2

Initial assignment of an IPv4 address

Configuration options
An initial IP address for an IE switch cannot be assigned using Web Based Management
(WBM) because this configuration tool can only be used if an IP address already exists.
The following options are available to assign an IP address to an unconfigured device:
● DHCP (default)
● Primary Setup Tool (PST)
– To be able to assign an IP address to the IE switch with the PST, it must be possible to
– You will find the PST on the Internet pages of Siemens Industry Online Support under
– For further information about assigning the IP address with the PST, refer to the
● STEP7
In STEP 7, you can configure the topology, the device name and the IP address. If you
connect an unconfigured IE switch to the controller, the controller assigns the configured
device name and the IP address to the IE switch automatically.
– STEP 7 as of V5.5 SP4
– STEP 7 Basic as of V12 SP1 or STEP 7 Professional as of V12 SP1
● CLI via the serial interface
For further information on assigning the IP address using the CLI, refer to the
documentation "SCALANCE XM-400/XR-500 Command Line Interface".
24
reach the device via Ethernet.
the entry ID 19440762
19440762).
documentation "Primary Setup Tool (PST)".
For further information on the assignment of the IP address using STEP 7 refer to the
documentation "Configuring Hardware and Connections with STEP 7", in the section
"Steps For Configuring a PROFINET IO System".
For further information on assigning the IP address using STEP 7 (as of V12 SP1), refer
to the online help "Information system", section "Addressing PROFINET devices".
(http://support.automation.siemens.com/WW/view/en/
SCALANCE XM-400/XR-500 Web Based Management (WBM)
Configuration Manual, 05/2017, C79000-G8976-C248-12