Description of the displayed values
The table has the following columns:
● Redundancy Function
The "Redundancy Function" column shows the role of the device within the ring:
– No Ring Redundancy (off)
– HRP Client
– HRP Manager
– MRP Client
– MRP Manager
– MRP Auto-Manager
● RM Status
The "RM Status" column shows whether or not the IE switch is operating as redundancy
manager and whether it has opened or closed the ring in this role.
– Passive:
– Active:
– If media redundancy in ring topologies is completely disabled, ring ports configured last
● Observer Status
Shows the current status of the observer.
● Ring Port 1 and Ring Port 2
The "Ring Port 1"and "Ring Port 2" columns show the ports being used as ring ports.
● No. of Changes to RM Active State
Shows how often the device as redundancy manager switched to the active status, i.e.
closed the ring.
If the redundancy function is disabled or the device is an "HRP/MRP client" , the text
"Redundancy Manager Disabled" appears.
SCALANCE XM-400/XR-500 Web Based Management (WBM)
Configuration Manual, 05/2017, C79000-G8976-C248-12
The IE switch works without redundancy function.
The IE switch operates as an HRP client.
The IE switch operates as an HRP manager.
The IE switch operates as an MRP client.
The IE switch operates as an MRP manager. Using STEP 7, the role "Manager" was
set for the device.
The IE switch is operating as an MRP manager. Using WBM or CLI the role "MRP Auto-
Manager" or using STEP 7 the role "Manager (Auto)" was set.
The IE switch is operating as redundancy manager and has opened the ring; in other
words, the line of switches connected to the ring ports is operating problem free. The
passive status is also displayed if the IE switch is not operating as the redundancy
manager (RM function disabled).
The IE switch is operating as redundancy manager and has closed the ring; in other
words, the line of switches connected to the ring ports is interrupted (problem). The
redundancy manager connects its ring ports through and restores an uninterrupted
linear topology.
are displayed and the text "Ring Redundancy disabled" is displayed.