Siemens SCALANCE X-000 Operating Instructions Manual
Siemens SCALANCE X-000 Operating Instructions Manual

Siemens SCALANCE X-000 Operating Instructions Manual

Industrial ethernet switches

Advertisement

SCALANCE X-000
SIMATIC NET
Industrial Ethernet switches
SCALANCE X-000
Operating Instructions
09/2016
C79000-G8976-C344-02
___________________
Introduction
___________________
Network topologies
___________________
Description of the device
___________________
Mounting
___________________
Connecting up
___________________
Maintenance and
troubleshooting
___________________
Technical specifications
___________________
Approvals
___________________
Dimension drawings
1
2
3
4
5
6
7
8
9

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SCALANCE X-000

  • Page 1 ___________________ SCALANCE X-000 Introduction ___________________ Network topologies ___________________ SIMATIC NET Description of the device ___________________ Mounting Industrial Ethernet switches SCALANCE X-000 ___________________ Connecting up ___________________ Maintenance and troubleshooting Operating Instructions ___________________ Technical specifications ___________________ Approvals ___________________ Dimension drawings 09/2016 C79000-G8976-C344-02...
  • Page 2: Legal Information

    Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 3: Table Of Contents

    On the Operating Instructions ....................5 On the product .......................... 7 Network topologies ..........................9 Description of the device ........................11 Overview SCALANCE X-000 ....................11 Product characteristics......................12 TP ports (twisted pair) ......................13 LEDs ............................16 Mounting ............................... 17 Safety notices for installation ....................
  • Page 4 Table of contents SCALANCE X-000 Operating Instructions, 09/2016, C79000-G8976-C344-02...
  • Page 5: Introduction

    The "SIMATIC NET Industrial Ethernet Twisted Pair and Fiber Optic Networks" manual contains additional information on other SIMATIC NET products that you can operate along with the SCALANCE X-000 IE switches in an Industrial Ethernet network. You can order the manual "SIMATIC NET Industrial Twisted Pair and Fiber Optic Networks",...
  • Page 6 Siemens recommends strongly that you regularly check for product updates. For the secure operation of Siemens products and solutions, it is necessary to take suitable preventive action (e.g. cell protection concept) and integrate each component into a holistic, state-of-the-art industrial security concept.
  • Page 7: On The Product

    Ethernet linear bus or star structures with switching functionality. The devices are designed for installation in a cabinet. Note It is not possible to use a SCALANCE X-000 in a redundant ring because it does not support redundancy. Note If devices are supplied over long 24 V power supply lines or networks, measures are necessary to prevent interference by strong electromagnetic pulses on the supply lines.
  • Page 8 2. Check all the parts for transport damage. Warning triangle on the type plate. This warning triangle on the type plate refers to the safety-relevant notes in the documentation. Read the operating instructions and note the safety-relevant information. SCALANCE X-000 Operating Instructions, 09/2016, C79000-G8976-C344-02...
  • Page 9: Network Topologies

    Switching technology allows extensive networks to be set up with numerous nodes and simplifies network expansion. Which topologies can be implemented? Using the SCALANCE X-000 IE switches, you can implement star topologies. Note Keep to the maximum permitted cable lengths of the devices you are using. You will find the permitted cable lengths in the section "Technical specifications (Page 33)".
  • Page 10 Network topologies SCALANCE X-000 Operating Instructions, 09/2016, C79000-G8976-C344-02...
  • Page 11: Description Of The Device

    Description of the device Overview SCALANCE X-000 Table 3- 1 Overview of the product characteristics X005 X005TS SIMATIC environment Diagnostics LED 24 VDC 2 x 24 VDC Compact housing (securing collar, etc.) Signaling contact + on-site operation Diagnostics: Web, SNMP, PROFINET...
  • Page 12: Product Characteristics

    Description of the device 3.2 Product characteristics Product characteristics Possible attachments The SCALANCE X-000 has five RJ-45 jacks for connection of end devices or other network segments. Figure 3-1 SCALANCE X005 Note The SCALANCE X005 shown above has the same construction as the SCALANCE X005TS.
  • Page 13: Tp Ports (Twisted Pair)

    Description of the device 3.3 TP ports (twisted pair) TP ports (twisted pair) RJ-45 connector pinout With SCALANCE X-000, the twisted-pair ports are designed as RJ-45 jacks with MDI-X pin assignment (Medium Dependent Interface Autocrossover) of a network component. Pin number Assignment Pin 8 n.
  • Page 14 If the pair of receiving cables is connected incorrectly (RD+ and RD- interchanged), the polarity is adapted automatically. Note The SCALANCE X-000 IE switches are plug-and-play devices that require no settings during commissioning. MDI / MDI-X autocrossover function With the MPI/MDI-X autocrossover function, the send and receive contacts of an Ethernet port are assigned automatically.
  • Page 15 The requirements for Environment A are met between ports of the same group, e.g. between P2 and P5. Devices without port groups The following devices do not have port groups: ● SCALANCE X005 6GK5 005-0BA10-1AA3 The requirements for Environment A are met between all ports. SCALANCE X-000 Operating Instructions, 09/2016, C79000-G8976-C344-02...
  • Page 16: Leds

    The port LEDs indicate the status of the ports. LED color LED status Meaning Green TP link exists, no data reception at port Yellow TP link exists, data reception at port Yellow Flashing Test phase during power on SCALANCE X-000 Operating Instructions, 09/2016, C79000-G8976-C344-02...
  • Page 17: Mounting

    Safety notices for use according to ATEX and IECEx If you use the device under ATEX or IECEx conditions you must also keep to the following safety notices in addition to the general safety notices for protection against explosion: SCALANCE X-000 Operating Instructions, 09/2016, C79000-G8976-C344-02...
  • Page 18: Types Of Installation

    50 ℃ to 75 ℃. Installation clearance Keep to the minimum clearances so that the convection ventilation of the device is not blocked. ● Below at least 10 cm ● Above at least 10 cm SCALANCE X-000 Operating Instructions, 09/2016, C79000-G8976-C344-02...
  • Page 19: Installation On A Din Rail

    3. Fit the connectors for the power supply. See also section "Power supply (Page 26)". 4. Insert the terminal block into the sockets on the device. Figure 4-1 Installation on a 35 mm DIN rail SCALANCE X-000 Operating Instructions, 09/2016, C79000-G8976-C344-02...
  • Page 20 3. Release the DIN rail catch on the bottom of the device using a screwdriver. 4. Pull the lower part of the device away from the DIN rail. Figure 4-2 Removal from a 35 mm DIN rail SCALANCE X-000 Operating Instructions, 09/2016, C79000-G8976-C344-02...
  • Page 21: Installation On A Standard Rail

    To remove the device from the S7-300 standard rail, follow the steps below: 1. Disconnect all connected cables. 2. Release the screw on the bottom of the standard rail. 3. Remove the device from the standard rail. SCALANCE X-000 Operating Instructions, 09/2016, C79000-G8976-C344-02...
  • Page 22: Wall Mounting

    3. Insert the terminal block into the sockets on the device. 4. Screw the device to the wall. Note The wall mounting must be capable of supporting at least four times the weight of the device. SCALANCE X-000 Operating Instructions, 09/2016, C79000-G8976-C344-02...
  • Page 23: Connecting Up

    If you use the device under HazLoc conditions you must also keep to the following safety notices in addition to the general safety notices for protection against explosion: WARNING EXPLOSION HAZARD DO NOT DISCONNECT WHILE CIRCUIT IS LIVE UNLESS AREA IS KNOWN TO BE NON-HAZARDOUS. SCALANCE X-000 Operating Instructions, 09/2016, C79000-G8976-C344-02...
  • Page 24 The LAN is designed either for “Environment A” according to IEEE802.3 or "Environment 0" according to IEC TR 62102. Do not connect any electrical connectors directly to the telephone network (telephone network voltage) or a WAN (Wide Area Network). SCALANCE X-000 Operating Instructions, 09/2016, C79000-G8976-C344-02...
  • Page 25: Wiring Rules

    ** See note "Wire end ferrules" Note Wire end ferrules Use crimp shapes with smooth surfaces, such as provided by square and trapeze shaped crimp cross sections. Crimp shapes with wave-shaped profile are unsuitable. SCALANCE X-000 Operating Instructions, 09/2016, C79000-G8976-C344-02...
  • Page 26: Power Supply

    Note The device can be disconnected from the power supply with the terminal block. The following figure shows the position of the power supply of the SCALANCE X-000 and the assignment of the terminal block. Contact...
  • Page 27: Grounding

    If the device is mounted on a non-conductive base, a grounding cable must be fitted. The grounding cable is not supplied with the device. Connect the paint-free surface of the device to the nearest grounding point using the grounding cable. SCALANCE X-000 Operating Instructions, 09/2016, C79000-G8976-C344-02...
  • Page 28: Ie Fc Rj-45 Plug 180

    Fitting the IE FC RJ45 Plug 180 to the IE FC Standard Cable You will find the notes on installation in the instructions that ship with the IE FC RJ45 Plug 180. Figure 5-1 IE FC 45 Plug 180 SCALANCE X-000 Operating Instructions, 09/2016, C79000-G8976-C344-02...
  • Page 29 If there is not enough space to release the lock with your hand, you can also use a 2.5 mm screwdriver. You can then remove the IE FC RJ45 Plug 180 from the RJ-45 jack. SCALANCE X-000 Operating Instructions, 09/2016, C79000-G8976-C344-02...
  • Page 30 Connecting up 5.5 IE FC RJ-45 Plug 180 SCALANCE X-000 Operating Instructions, 09/2016, C79000-G8976-C344-02...
  • Page 31: Maintenance And Troubleshooting

    LEDs are off despite correctly applied power supply), the device should be disconnected from the power supply for approximately 30 minutes before turning it on again. Device defective If a fault develops, please send the device to your SIEMENS service center for repair. Repairs on-site are not possible. SCALANCE X-000...
  • Page 32 Maintenance and troubleshooting SCALANCE X-000 Operating Instructions, 09/2016, C79000-G8976-C344-02...
  • Page 33: Technical Specifications

    18 to 32 VDC Safe Extra Low Voltage (SELV) Design 2-terminal plug-in block Current consumption Typical 80 mA Power loss at 24 VDC Typical Overvoltage protection at input PTC resettable fuse (0.5 A / 60 V) Permitted ambient conditions SCALANCE X-000 Operating Instructions, 09/2016, C79000-G8976-C344-02...
  • Page 34 Max. number of learnable MAC ad- 1024 dresses Response to LLDP frames Blocking Response to spanning tree BPDU Forwarding frames CoS acc. to IEEE 802.1Q QoS priority queues IEEE 802.1Q tags (VLAN ID, priority) transparent forwarding SCALANCE X-000 Operating Instructions, 09/2016, C79000-G8976-C344-02...
  • Page 35 18 to 32 VDC Safe Extra Low Voltage (SELV) Design 2-terminal plug-in block Current consumption Typical 60 mA Power loss at 24 VDC Typical 1.5 W Overvoltage protection at input PTC resettable fuse (0.5 A / 60 V) SCALANCE X-000 Operating Instructions, 09/2016, C79000-G8976-C344-02...
  • Page 36 Max. number of learnable MAC ad- 1024 dresses Response to LLDP frames Blocking Response to spanning tree BPDU Forwarding frames CoS acc. to IEEE 802.1Q QoS priority queues IEEE 802.1Q tags (VLAN ID, priority) transparent forwarding SCALANCE X-000 Operating Instructions, 09/2016, C79000-G8976-C344-02...
  • Page 37 • with a 64 byte frame length by approx. 10 µs (at 100 Mbps) • with a 1500 byte frame length by approx. 130 µs (at 100 Mbps) This means that the more SCALANCE X005 the frame passes through, the longer the frame delay. SCALANCE X-000 Operating Instructions, 09/2016, C79000-G8976-C344-02...
  • Page 38 Technical specifications SCALANCE X-000 Operating Instructions, 09/2016, C79000-G8976-C344-02...
  • Page 39: Approvals

    ● "Industrial Ethernet / PROFINET - Passive network components" System Manual You will find information on the system manuals in the section "Auto-Hotspot", in "Further documentation". ● "EMC Installation Guidelines" configuration manual 60612658 (http://support.automation.siemens.com/WW/view/en/60612658) SCALANCE X-000 Operating Instructions, 09/2016, C79000-G8976-C344-02...
  • Page 40 You will find the EC declaration of conformity for these products on the Internet pages of Siemens Industry Online Support (http://support.automation.siemens.com/WW/view/en/33118389/134200). The EC Declaration of Conformity is available for all responsible authorities at:...
  • Page 41 Area". You will find this document • on the data medium that ships with some devices. • on the Internet pages of Siemens Industry Online Support (http://support.automation.siemens.com/WW/view/en). Enter the document identification number C234 as the search term. The SIMATIC NET products meet the requirements of the EC directive 94/9/EC "Equipment and Protective Devices for Use in Potentially Explosive Atmospheres”.
  • Page 42 The IE switch SCALANCE X005TS meets the requirements of the directive ECE R10, Rev. Test number: 10 R - 024733 EC directive The SCALANCE X005TS IE switch meets the requirements of the Directive 72/245/EEC in the form 2006/96/EC "Electromagnetic Compatibility". SCALANCE X-000 Operating Instructions, 09/2016, C79000-G8976-C344-02...
  • Page 43 DIN EN 60068-2-27 shock 10 - 58.12 Hz: 0.075 mm 150 m/s , 11 ms duration 58.12 - 500 Hz: 10 m/s 6 shocks per axis 10 cycles SCALANCE X005 ● ● SCALANCE X005TS ● ● SCALANCE X-000 Operating Instructions, 09/2016, C79000-G8976-C344-02...
  • Page 44 Approvals SCALANCE X-000 Operating Instructions, 09/2016, C79000-G8976-C344-02...
  • Page 45: Dimension Drawings

    Dimension drawings Figure 9-1 Dimension drawing, rear of the SCALANCE X-000 SCALANCE X-000 Operating Instructions, 09/2016, C79000-G8976-C344-02...
  • Page 46 Dimension drawings Figure 9-2 Dimension drawing, side view of SCALANCE X-000 SCALANCE X-000 Operating Instructions, 09/2016, C79000-G8976-C344-02...
  • Page 47: Index

    Permitted ambient conditions, 33, 36 Installation on a DIN rail, 27 Permitted cable lengths, 13, 33, 35 S7 standard rail, 27 Pin assignment Wall mounting, 27 SCALANCE X005, 13 SCALANCE X005TS, 13 Port LEDs, 16 SCALANCE X-000 Operating Instructions, 09/2016, C79000-G8976-C344-02...
  • Page 48 Switching properties, 34, 36 System manual, 39 Technical specifications Connector, 33, 35 Design, dimensions and weight, 34, 36 Electrical data, 33, 35 Permitted ambient conditions, 33, 36 Permitted cable lengths, 33, 35 Switching properties, 34, 36 SCALANCE X-000 Operating Instructions, 09/2016, C79000-G8976-C344-02...

Table of Contents