Specifications - Lenel OnGuard Hardware Installation Manual

Table of Contents

Advertisement

12

Specifications

The LNL-500 is for use in low voltage, class 2 circuits only.
Primary Power: (DC or AC)
DC input: 12 VDC ± 10%. 250 mA
-
AC input: 12 VAC ± 15%. 400 mA RMS
-
Memory and Clock Backup: 3 V lithium, type BR2325
Communication Ports:
-
Port 1: RS-232 or RS-485, 9600 to 38400 bps async
-
Ports 2-3: RS-485 (2-wire), 9600 to 38400 bps async
Inputs:
-
Cabinet Tamper Monitor: unsupervised, dedicated
-
Power Fault Monitor: unsupervised, dedicated
Wire Requirements:
-
Power: 1 stranded twisted pair, 18 AWG
-
RS-485: 24 AWG stranded twisted pair(s) with shield, 4000 feet (1219 m) maximum
-
RS-232: 24 AWG stranded, 50 feet (15.24 m) maximum
-
Alarm Input: stranded twisted pair, 30 ohms maximum
Environmental:
-
Temperature: Operating: 0° to +70° C (32° to 158° F)
-
Humidity: 0 to 95% RHNC
Mechanical:
-
Dimension: 6 x 5 x 1 in. (152 x 127 x 25 mm)
-
Weight: 8 oz. (227 g) nominal
Data Memory: 512 KB
Certifications:
-
UL294 & UL1076 Listed
-
ULC Listed
-
FCC Part 15
-
C-Tick
-
FIPS 197 Certificate #305
-
CE marking
-
RoHS compliant
-
WEEE
Note:
These specifications are subject to change without notice.
Hardware Installation Guide
revision 7 —