Use the LPMR-1824 MC, the metal-compensated form of the LPMR-1824 reader only when
nearby metal will reduce the performance of the standard LPMR-1824 reader.
When using the LPMR-1824 MC reader, it should be mounted on a metal surface that is larger
than the 8 x 8 inch reader housing. Lenel recommends a metal surface of 12 square inches or
larger.
2.
If you are installing the LPMR-1824, SKIP THIS STEP and proceed to step 3!
To mount the LPMR-1824 MC reader on the metal surface:
a.
Remove the four screws through the front of the reader's plastic housing. This releases the four
ferrite tiles from the back of the reader.
b.
Use the ferrite tiles as templates for mounting holes on the wall or other surface. These holes are at
the center of each 4 x 4-inch tile. The center of the hole is two inches from each edge.
c.
If necessary, enlarge the hole in the ferrite tiles slightly by drilling or reaming.
d.
Screw the reader's plastic base and the ferrite tiles to the wall by inserting the 4 screws first through
the inside of the plastic base, then through the holes in the ferrite tiles, then into the mounting holes
in the wall.
e.
Reattach the reader's plastic cover using the screws that were removed in step a.
3.
Clip off the white in-line connector from the end of the reader's cable. Keep the wires as long as
possible.
Holes location
Hardware Installation Guide