Installation; Wiring And Setup - Lenel OnGuard Hardware Installation Manual

Table of Contents

Advertisement

LNL-2220 Intelligent Dual Reader Controller
29

Installation

To install the IDRC, perform the installation procedures described in the following sections, in the order in
which they are presented.
1.
Wire the device for communication.
2.
Wire readers, if applicable.
3.
Wire the input circuit.
4.
Wire the relay circuit.
5.
Supply power to the controller and wire the unsupervised alarm inputs for power fault and cabinet
tamper monitoring.
6.
Remove the plastic safety strip from the memory backup battery.
7.
Configure the correct settings using the jumpers and DIP switches.
8.
Set the board for the desired initial IP addressing mode.
9.
Configure the network and port settings using the embedded web server.
29.1

Wiring and Setup

Refer to the following table for wiring and setup of the LNL-2220.
Connection
TB1
Power input
Cabinet tamper input
Power fault input
TB2
Host port 1
TB3
Downstream port
148 —
revision 7
VIN: 12 to 24 VDC
GND
TMP
GND
FLT
GND
TXD (RS-232)
RXD (RS-232)
RTS (RS-232)
CTS (RS-232)
GND (RS-232)
TR+ (2-wire RS-485)
TR- (2-wire RS-485)
GND(2-wire RS-485)