Biometric Readers
2.
Enable the port using the Unit Parameter Settings window. The settings will be different for enrollment
readers and verification readers.
a.
The General tab displays the product, firmware, communication, and template information for the
current reader.
b.
On the Communication tab, select Enable Port. The settings for an enrollment reader are shown
below.
Network Identification Number: Assign the unit a network ID number. This can be any value
from 0-7. This value corresponds to the address of the reader.
Host Port Protocol: This needs to be set to RS-485.
Host Port Baud Rate: This can be set to either 38400 or 9600 baud.
For a verification reader, the mode and baud rate must be changed. These settings must match the
settings configured on the gateway and in the access control software.
650 —
revision 7