Overview Of The Lnl-1300E; The Lnl-1300E Ip Interface Board - Lenel OnGuard Hardware Installation Manual

Table of Contents

Advertisement

66

Overview of the LNL-1300e

This reader IP interface provides a network-connected, single door, PoE-based solution using single or
paired readers for ingress/egress operation. The first reader port can accommodate a read head that utilizes
Wiegand, magnetic stripe, or 2-wire RS-485 electrical signaling standards, one or two wire LED controls,
and buzzer control (one-wire LED mode, only).
The second reader port can accommodate a read head that utilizes Wiegand or magnetic stripe signaling, one
or two-wire LED controls, and buzzer control (one-wire LED mode, only). Two Form-C relay outputs may
be used for door strike control or alarm signaling. The relay contacts are rated at a 5 Amp @ 30 VDC, dry
contact configuration. Four (4) inputs are provided for monitoring the door contacts, exit push buttons, and
alarm contacts. The LNL-1300e requires power from PoE or local 12 VDC.
Notes:
An alternative configuration of the LNL-1300e is available where no reader ports are used, and
the device is deployed as an alarm panel with 4 inputs and 2 relay outputs.
This product has been evaluated by UL for access control applications only.
The LNL-1300e may be mounted in a UL Listed 3-gang switch box (a mounting plate is supplied with the
unit). The controller may be mounted in an enclosure; the supplied mounting plate has mounting holes that
match the LNL-1300 mounting footprint.
66.1

The LNL-1300e IP Interface Board

The board contains the following components: one (1) host Ethernet interface, one (1) power-in input, four
(4) unsupervised/supervised inputs, two (2) reader interfaces, two (2) output relays, four (4) DIP switches,
seven (7) jumpers, six (6) status LEDs, and one (1) reset switch.
66.1.1
Support for LNL-1300e
Access panel support for the LNL-1300e includes the LNL-2210/2220/3300/3300-M5. Access panels must
be configured for IPv4 communication mode.
Maximum number of LNL-1300e addressable devices allowed per port:
8 for the LNL-2210
32 for the LNL-2220/3300/3300-M5
Hardware Installation Guide