Can/Ulc-S319-05 Requirements - Lenel OnGuard Hardware Installation Manual

Table of Contents

Advertisement

Hardware Installation Guidelines
When using dial-up connection, a dedicated phone line must be used. The modem connection must be
maintained continuously.
When using the Securecomm Uniflex DC336 modem, it must be in a secured box and powered by a
power supply UL/ULC Listed for Access Control/Proprietary Burglar Alarm Systems, and power-
limited.
The relays on the LNL-1300 can only be used for access control applications.
For the LNL-1300, field wiring for relay K2 should not extend beyond the room of installation.
The following devices/methods of communication have NOT been evaluated by UL:
CoBox Token Ring Serial Server
HID Edge devices
Lantronix CoBox-DR
LNL-IC108A/IC109A
LNL-838A converter
Cypress Timer
ILS locks
5.4

CAN/ULC-S319-05 Requirements

Only OnGuard 7.0 (7.0.xxx), OnGuard 7.1 (7.1.xxx), OnGuard 7.2 (7.2.xxx), and
OnGuard 7.3 (7.3.xxx) Monitoring Software was evaluated for use.
Portal locking devices must be ULC or cUL Listed, and be constructed so that they do not interfere with
egress, with their locking action capable of being released when emergency egress is required.
Compliance with this requirement will be determined by demonstrating operability with ULC-S533,
Standard for Egress Door Securing and Releasing Devices, compliant devices. If the application
requires fire resistance, devices will be both ULC-S533 and ULC-CAN4-S104, Standard Method for
Fire Tests of Door Assemblies, compliant.
Installation must be in accordance with CSA 22.1, National Electrical Code.
RS-485 cable must be shielded.
Pass codes used with keypads will be system generated or generated by a system administrator, and the
maximum number of users shall not exceed 500 (for Class II).
An electronic access control system operated from commercial power shall be provided with standby
power with capacity of 7 Ah or 18 Ah to support a full load for a period of 30 minutes (Class II), in the
event of primary power loss.
Front and rear tampers must be used. A visual and/or audible alarm shall be annunciated if the enclosure
is tampered.
All card readers must be evaluated by UL, must be ULC or cUL Listed, and be Wiegand compatible.
This Class B digital apparatus complies with Canadian ICES-003.
54 —