Lenel OnGuard Hardware Installation Manual page 350

Table of Contents

Advertisement

LNL-1300 Single Reader Interface Module
ADDRESS
1:
27
ON
28
off
29
ON
30
off
31
ON
64.1.2
Communication Baud Rate
To configure the communication baud rate, set jumpers 6 and 7 according to the following table.
BAUD RATE:
38400 bps
ON
19200 bps
off
9600 bps
ON
2400 bps
off
Currently, OnGuard only supports a baud rate of 38400 bps, so be sure to set both 6 and 7 to the ON
position.
64.1.3
Communication Password Status
Jumper 8 controls the utilization of encryption.
PASSWORD STATUS
Encryption is optional
Encryption is required
When jumper 8 is ON, communication will not be allowed unless the access panel supports downstream
encryption and is configured to enable encryption to this device.
When jumper 8 is off, the device will accept either encrypted or unencrypted communication. It must be off
if the access panel does not support downstream encryption, or if downstream encryption is disabled for this
device.
64.1.4
Cabinet Tamper
Jumper J3 is used to configure cabinet tamper. There are two possible configuration options: On or Off.
When J3 is on, cabinet tamper is bypassed. When it is off, it must be wired in order to work.
350 —
revision 7
JUMPER
2:
3:
4:
ON
off
ON
off
ON
ON
off
ON
ON
ON
ON
ON
ON
ON
ON
JUMPER
6:
7:
ON
ON
off
off
DIP SWITCH 8:
(OnGuard 2009 or later)
off
ON
5:
ON
ON
ON
ON
ON
DIP SWITCH 8:
(prior to OnGuard 2009)
Normal operation
Not allowed