89

Specifications

Note:
For UL installations, refer to section
The LNL-1320 is for connection to low voltage, class 2 power-limited circuits only. These specifications are
subject to change without notice.
Primary power: 12 to 24 VDC + 10%
-
12 VDC @ 1200 mA (includes reader current) nominal
-
24 VDC @ 600 mA (includes reader current) nominal
-
49.1 BTU/hour
Outputs: Form-C contacts, Relays 1-6 (K1-K6), 5 A @ 30 VDC
Inputs:
-
Eight (8) supervised, End of Line resistors, 1k/1k ohm, 1% 1/4 watt standard
-
One (1) unsupervised, dedicated external (cabinet) tamper
-
One (1) unsupervised, AC power fail
Reader interface:
-
Reader power (per reader): voltage 12 VDC +/-10% (optional 5 VDC +/-5% jumper selectable,
current 400 mA maximum to 50°C, derate to 300 mA for 70°C)
-
Reader LED output: open collector type switching (sinking) 10 mA each
-
Reader buzzer output: open collector type switching (sinking) 10 mA each
-
Reader data inputs: 2-wire RS-485, Wiegand Data1/Data0, Clock and Data
-
Does not support Bioscrypt readers or the LNL-CK keypad
Upstream communication: RS-485, 2-wire, 2400 to 38400 bps
-
Does not support encryption
Downstream communication:
-
Does not support RS-485
Cable requirements:
-
Power: 18 AWG, 1 stranded twisted pair
-
RS-485: 24 AWG, 120 ohm impedance, stranded twisted pair with shield, 4000 feet [1219m]
maximum
-
Alarm inputs: 1 stranded twisted pair per input, 30 ohms maximum
-
Outputs: As required for the load
-
Reader data (Wiegand, Clock and Data): 6 conductors, 18 AWG stranded, 500 feet [150m]
maximum
-
Reader data (RS-485): 24 AWG, 120 ohm impedance, stranded twisted pair with shield, 4000 feet
[1219m] maximum
Mechanical:
-
Dimension: 5 x 8 x 1.25 in. (127 x 203 x 32 mm)
-
Weight: 7.3 oz. (207 g) nominal
Environmental:
-
Temperature: -10 to +70°C (14 to 158°F) operating, -40 to +85°C (-40 to 185°F) storage
-
Humidity: 10% at 93°C (199°F) non-condensing operating, 10 to 95% at 85°C (185°F) non-
condensing storage
Certifications:
-
FCC Part 15
UL Listed Installations