Specifications - Lenel OnGuard Hardware Installation Manual

Table of Contents

Advertisement

LNL-2000 Intelligent System Controller
22

Specifications

**The LNL-2000 is for use in low voltage, class 2 circuits only.
Primary Power: (DC or AC)
-
DC input: 12 VDC + 10%, 400 mA (550 mA with NIC) recommended
-
AC input: 12 VAC + 15%, 650 mA RMS (800 mA RMS with NIC)
Memory and Clock Backup: 3 Volt Lithium, Rayovac BR2325 or Wuhan Lixing CR2330
Data Memory: 1 MB standard (optional memory module) available
Ports:
-
Port 1, 6: RS-232 or RS-485, 9600 to 115,200 bps, async
-
Port 2-5: RS-485, 2-wire, 2400 to 38400 bps, async
Inputs: two unsupervised, dedicated, for local tamper
-
Power:1 stranded twisted pair, 18 AWG
-
RS-485: 24 AWG, 4000 feet (1200 m) max., stranded twisted pair(s) with shield.
-
RS-232: 24 AWG stranded, 50 feet (15.24 m) max.
-
Alarm input: 1 stranded twisted pair, 30 ohms max.
Environmental:
Temperature: 0 to 70 ° C operating, -55 to +85° C storage
-
-
Humidity: 0 to 95% RHNC
Mechanical:
-
Dimensions: 6 x 8 x 1 in. (152 x 203 x 25 mm)
-
Weight: 10 oz. (284 g) nominal
Certifications:
-
UL294 & UL1076 Listed
-
ULC Listed
-
FCC Part 15
-
C-Tick
-
FIPS 197 Certificate #307
-
CE marking
-
RoHS compliant
-
WEEE
Note:
These specifications are subject to change without notice.
112 —
revision 7

Advertisement

Table of Contents
loading

Related Products for Lenel OnGuard

Table of Contents