Mifare/Iclass Handkey Reader - Lenel OnGuard Hardware Installation Manual

Table of Contents

Advertisement

HandKey Readers
10. You will then be asked to set the baud rate for channel 0 (RS-485 baud rate). Set the baud rate to match
the setting of the biometric reader interface. You will be prompted for a baud rate code (the default is
usually 19.2 Kbps). Enter a single digit for the desired baud rate according to the following table.
BAUD RATE
CODE
38400
0
9600
2
2400
4
600
6
11. You will also be prompted for the baud rate of channel 1 (RS-232 baud rate). This is not applicable for
verification mode on this reader.
12. To exit from the menu, press the any number button when the reader displays the * NO YES # prompt.
HandKey ID3D-R Reader DIP Switches
The DIP switches need to be set properly for RS-485 communication. For more information, please refer to
the HandKey Installation Manual.
ID3D DIP
Description
Switch
1
EOL termination for RS-422 (To enable EOL termination, turn this DIP switch ON.)
2
EOL termination for RS-485 (To enable EOL termination, turn this DIP switch ON.)
3
Selects RS-485 (This DIP switch should be ON for all verification readers.)
4
Erases configuration
112.1.8
HandKey Reader Operation
For more detailed information, please refer to your Schlage HandKey Installation and Operation Manual.
The hand reader is ordinarily used in conjunction with a primary reader. To gain access, cardholders must
present their badge and then place their hand on the hand reader's platen.
If the access control software is configured for use of card or PIN, the keypad of the hand reader may
alternately be used. Enter the PIN, followed by the [#] key or [Enter] key. The hand reader will then prompt
users to place their hand on the platen. The Schlage unit supports up to 9 digits for the PIN code. Leading
zeroes are not supported.
Note:
Currently, keypad commands using the [*] key are not supported.
112.2

MIFARE/iCLASS HandKey Reader

Along with the hand geometry, the readers have the added MIFARE or iCLASS functionality.
594 —
revision 7
BAUD RATE
CODE
19200
1
4800
3
1200
5
300
7