Lenel OnGuard Hardware Installation Manual page 271

Table of Contents

Advertisement

Use sufficiently large gauge of wires for the load current as to avoid voltage loss.
NC
C
NO
NO
NC
C
NC
C
NO
NO
NC
C
43.1.5
Power
For the LNL-1100 series 2, the power source should be located as close to module as possible.
Wire the power input with an 18 AWG (minimum) twisted pair cable.
Note:
Be sure to observe polarity.
12 VDC
+
-
DIODE 1N4002 (100 V/1A) TYPICAL
DIODE CURRENT RATING > 1X STRIKE CURRENT
DIODE BREAK DOW N VOLTAGE > 4X STRIKE VOLTAGE
AC
XFMR
FOR 24 VAC STRIKE, PANASONIC ERZ-C 07 DK470
MOV SELECTION:
CLAMP VOLTAGE > 1.5 X VAC RMS
+
VIN
12 to 24 VDC
GND
-