Jumper J17 pins 1 & 2 for +12VDC readers
Jumper J17 pins 2 & 3 for +5VDC readers
Reader 1 RS-485 termination:
Jumper J29 pins 1 & 2 for RS-485 reader communications.
Important:
Reader 2 RS-485 termination:
Jumper J31 pins 1 & 2 for RS-485 reader communications.
Important:
Reader 1 data line pull-up voltage selection:
Jumper J9 pins 1 & 2 for +12VDC Data Lines
Jumper J9 pins 2 & 3 for +5VDC Data Lines
Note:
Not required for RS-485 communications.
Reader 2 data line pull-up voltage selection:
Jumper J14 pins 1 & 2 for +12VDC Data Lines
Jumper J14 pins 2 & 3 for +5VDC Data Lines
Note:
Not required for RS-485 communications.
Jumpers J30 & J32 not used.
86.3

Status LEDs

Note:
The status LEDs only function when the cabinet tamper switch is open (cabinet door is open).
When the cabinet tamper switch is closed (cabinet door is closed), the status LEDs are off.
Do NOT install the jumper for Wiegand/Clock & Data/F2F Reader
Communications.
Do NOT install the jumper for Wiegand/Clock & Data/F2F Reader
Communications.