You will now be back at the setup screen. Type 2 and then press the <Enter> key to enter the serial port
setup menu. For each item, enter the following value.
Item
Baud rate
I/F mode
Flow control
Port #
Connect mode
Remote IP address
Remote port
Disconnect mode
Flush mode
Disconnect time
Send char 1
Send char 2
3.
You will now be back at the setup screen. Type 9 and then press the <Enter> key to save the setup
information and exit the CoBox setup menus.
4.
The device is now configured to work with the network. Power the machine down, connect it to the
network, and then power it up.
Step 3: Connecting the ISC to the CoBox Device
1.
Connect the ISC to the CH2 port of the CoBox device using a direct connection cable according to the
cable pinout table below.
Cable Pinouts
ISC
9-pin female
TXD/TR1+
pin 2
RXD/TR1-
pin 3
RTS/R1+
not used
CTS/R1-
pin 7
GND
pin 5
Jumper together
4,6 & 8
2.
Add the panel in the System Administration application, using the IP address of the CoBox. This is the
same IP address that was entered in Step 1, procedure number 10.
3.
Run the Access Control Driver and Alarm Monitoring applications. Verify that the panel came online.
226 —
revision 7
Value
38400
4C
00
03001
C1
0.0.0.0
00000
00
11
00:00
00
00