Lenel OnGuard Hardware Installation Manual page 345

Table of Contents

Advertisement

1
Supervised F/2F Board Edge Wiring Callouts
Callout
Description
1
Supervised F/2F reader
2
TB4 on LNL-1300
3
TB4-1: Ground connection
4
TB4-2: Buzzer terminal to Reader DO (GREEN LED) connection
5
For Supervised F/2F readers: Install jumper between D1 and LED terminals.
6
TB4-4: Reader Data 1 connection
7
TB4-6: +12 VDC connection
63.1.6
Open Supervised Device Protocol
Open Supervised Device Protocol (OSDP) uses bi-directional communications between readers and the
reader interface, providing constant monitoring of reader health, improved control of reader operation and
configuration in real-time, and additional communications capabilities over a single connection, including
biometric template download and LCD reader display control. For OSDP, set the baud rate to 9600 bps.
Supervised F/2F Board Edge Wiring
2
3
4
5
6
7