Lenel AES Firmware v1.02 is "extended" firmware that is embedded (installed) in conjunction with
Intelligent System Controllers (ISC), models LNL-500, LNL-1000, LNL-2000 (firmware version 3.085 or
later), models LNL-2220, LNL-3300, LNL-4420 (firmware version 1.068 or later) for suitability as
"Encrypted Line Security Equipment."
Network addressing of devices shall not make use of public domain name servers.
Panic hardware must be UL 305/ULC-S132 Listed.
5.1

Power

The standby power system for the HVAC system may be supplied by an engine driven generator alone. Use
of a standby battery is not required.
All external interconnecting power sources must be UL/ULC Listed access control/proprietary burglary
power limited power supplies. AC supply lines shall not be routed in the same conduit or harness as low
voltage lines.
5.1.1
UL/ULC Certified Power Supplies
For the UL certification, the power supply that must be used is the LNL-AL400ULX or
LNL-AL600ULX-4CB6 with additional hardware mounted in LNL-CTX or LNL-CTX-6 enclosures. Other
power supplies will be certified for use at a future date.
For the ULC Certification, hardware must be mounted in LNL-CTX or LNL-CTX-6 enclosures. All power
supplies must be UL, ULC, or cUL Listed for security applications, and power-limited.
Output
LNL-AL400U
12 VDC/
LX
40 AH Battery
LNL-AL600U
12 VDC/
LX-4CB6
40 AH Battery
5.2

Typical Combinations for UL Installations

The following combinations must be used in a UL type installation with OnGuard software versions 7.0.xxx,
7.1.xxx, 7.2.xxx, or 7.3.xxx which are approved for use. For UL certification, a UL Listed power supply,
either LNL-AL400ULX or LNL-AL600ULX-4CB6 with additional hardware mounted in LNL-CTX or
LNL-CTX-6 enclosures, must be used.
Multiple combinations of Lenel access hardware can be used within the UL approved power supply and
enclosure.
4 hr. of Stand-by &
24 hr. of Stand-by
5 minutes of Alarm
& 5 Minutes of
Alarm
Stand-by = 4.0 amps
Stand-by = 1.0 amp
Alarm = 4.0 amps
Alarm = 4.0 amps
Stand-by = 6.0 amps
Stand-by = 1.0 amp
Alarm = 6.0 amps
Alarm = 6.0 amps
Hardware Installation Guide
60 hr. of Stand-by
& 5 Minutes of
Alarm
Stand-by = 300 mA
Alarm = 4.0 amps
Stand-by = 300 mA
Alarm = 6.0 amps
revision 7 —