Specifications - Lenel OnGuard Hardware Installation Manual

Table of Contents

Advertisement

LNL-1300 Single Reader Interface Module
65

Specifications

The LNL-1300 series 2 is for use in low voltage, class 2 circuits only.
Primary power: 12 to 24 VDC + 10%, 150mA maximum (plus reader current)
-
12 VDC @ 110mA (plus reader current) nominal
-
24 VDC@ 60mA (plus reader current) nominal
Outputs: Form-C contacts: K1: 5A @ 28 VDC, K2: 1A @ 28 VDC
Inputs:
-
2 supervised, End of Line resistors, 1k/1k ohm, 1% 1/4 watt standard
-
1 unsupervised, dedicated for cabinet tamper
Reader Interface:
-
Reader power: 12 to 24 VDC ± 10% (input voltage passed through)
-
Reader LED output: TTL compatible, high > 3V, low < 0.5V, 5mA source/sink maximum
-
Buzzer output: Open collector, 5 VDC open circuit maximum, 10mA sink maximum
-
Reader data inputs: TTL compatible inputs or 2-wire RS-485
Communication: RS-485, 2-wire. 9600, 19200, 38400, or 115200 bps
Cable requirements:
-
Power: 18 AWG, 1 stranded twisted pair
-
RS-485: 24 AWG, 120 ohm impedance, stranded twisted pair with shield, 4000 feet (1219 m)
maximum
-
Alarm Inputs: 1 stranded twisted pair per input, 30 ohms maximum
-
Outputs: As required for the load
-
Reader data (TTL): 18 AWG stranded, 6 conductor, 500 feet (150 m) maximum
-
Reader data (RS-485): 24 AWG stranded, 120 ohm impedance, twisted pair with shield, 2000
(609.6 m) maximum
Mechanical:
-
Dimension: 4.25 x 2.75 x 1.4 in. (108 x 74 x 36 mm)
-
Weight: 4 oz. (120 g) nominal
Environmental:
-
Temperature: -55 to +85° C storage, -35 to +75° C operating
-
Humidity: 0 to 95% RHNC
Certifications:
-
UL294 & UL1076 Listed
-
ULC Listed
-
FCC Part 15
-
C-Tick
-
CE marking
-
RoHS compliant
-
WEEE
These specifications are subject to change without notice.
352 —
revision 7