60.6

UL Listed Installations

For UL installations, the following must be observed:
All field wiring terminals are suitable for single wire only.
Use 22 AWG minimum for wiring RS-485.
RS-485 4-wire is "Not Evaluated by UL" and therefore cannot be used in UL Installations.
The use of AC Strike is "Not Evaluated by UL" and therefore cannot be used in UL installations.
Environmental for UL installations:
-
Temperature: -10 to +49°C (14 to 120°F) operating
-
Humidity: 85+/-5% at 30+/-2°C (86°F)
Power source wiring