105.2.1
Installing the Reader
Note:
Before installing readers, the reader names should be imported using a template. Reader names
are not automatically duplicated or synchronized with the OnGuard configuration, so make
sure the names match correctly.
1.
Using the DirectKey Toolkit, install the reader by choosing its serial number. You will only be able to
select a reader that is unassigned.
2.
For Owner, select the name of the company or site where the reader will be installed.
3.
For Room Num, select the name for the reader.
105.3

Specifications

The readers are for use in low voltage, class 2 circuits only. These specifications are subject to change
without notice.
Primary Power:
-
Voltage: 5 to 16 VDC
-
Current: 250 mA typical
Cable Requirements:
-
RS-485: 18 AWG stranded twisted pair(s) with an overall shield, 500 feet (152.4 m) maximum
Environmental:
-
Temperature: Operating: -20° to +60° C (-4° to 140° F)
-
Humidity: 0 to 100% RHNC
Mechanical:
-
Dimensions:
LNL-R11320-05TB: 4.2 x 3.0 x 0.8 in. (120 x 76 x 21 mm)
-
Molded polycarbonate, gloss finish, black
Certifications:
-
UL294 & UL1076 Listed
-
CE marking
-
RoHS compliant
Hardware Installation Guide
549
revision 7 —