LNL-1100-U Input Control Module
LED Mode
SW1 switch 5 is used for LED control. It is read at boot time. If you make a change to this setting, be sure to
restart.
Note:
The status LEDs only function when the cabinet tamper switch is open (cabinet door is open).
When the cabinet tamper switch is closed (cabinet door is closed), the status LEDs are off.
SW1 Switch 5
State
ON
LEDs behave as the Access (LNL) series module.
off
LED behavior is in Normal Mode
48.1.2
Device Address (SW2)
Configure the board address using SW2. (Switches 6-8 are not used.)
Address
SW2 switch
1:
0
off
1
ON
2
off
3
ON
4
off
5
ON
6
off
7
ON
8
off
9
ON
10
off
11
ON
12
off
13
ON
14
off
15
ON
16
off
17
ON
284 —
revision 7
2:
3:
4:
off
off
off
off
off
off
ON
off
off
ON
off
off
off
ON
off
off
ON
off
ON
ON
off
ON
ON
off
off
off
ON
off
off
ON
ON
off
ON
ON
off
ON
off
ON
ON
off
ON
ON
ON
ON
ON
ON
ON
ON
off
off
off
off
off
off
5:
off
off
off
off
off
off
off
off
off
off
off
off
off
off
off
off
ON
ON