80.2.1
Status LEDs
The series 2 Dual Reader Interface Module board contains LEDs that can be used to verify correct
installation after power up.
The A LED is turned on at the beginning of initialization. If the application program cannot be run, the A
LED will flash at a rapid rate. The dual reader interface module is waiting for firmware to be downloaded.
When initialization is completed, LEDs A through R2 are briefly sequenced ON then OFF.
After the above sequence, the LEDs have the following meanings:
LED
Purpose
A
This LED is the heartbeat and online status.
Offline: 1 second rate, 20% ON
Online: 1 second rate, 80% ON
B
Indicates communication activity on the communication port.
1
IN1 input status
2
IN2 input status
3
IN3 input status
4
IN4 input status
5
IN5 input status
6
IN6 input status
7
IN7 input status
8
IN8 input status
TMP
Cabinet tamper
PFL
Power fault
Input in the inactive state: OFF (briefly flashes ON every 3 seconds).
Input in the active state: ON (briefly flashes OFF every 3 seconds).
Input in a trouble state (default): Rapid Flash.
R1: reader port 1:
Clock/Data Mode: Flashes when data is received, either input.
Data 0/Data 1 Mode: Flashes when data is received, either input.
RS-485 Mode: Flashes when transmitting data.
R2: reader port 2:
Clock/Data Mode: Flashes when data is received, either input.
Hardware Installation Guide
407
revision 7 —