Hardware Revision And Firmware - Lenel OnGuard Hardware Installation Manual

Table of Contents

Advertisement

Command Keypad
Configuration at the
Command Keypad
Use the Setup mode in the command keypad to make the following configuration settings. For more
information, refer to
Command Keypad Configuration
1.
Disconnect and then reconnect the +12 VDC power.
2.
When the screen displays "Press two keys for Setup," simultaneously press the keys indicated to enter
the setup screen. Follow the instructions on the LCD and press the [Configure] key.
3.
Make the following settings and press the [Accept] key after each setting is made:
-
Communication: Set to RS-485.
-
Baud Rate: Set to 9600 bps.
Note:
If the command keypad is connected to the downstream reader interface module, set the baud
rate to 9600 bps. If the command keypad is connected directly to the controller, set the baud
rate to 38400 bps.
-
Protocol: Set to MSP1.
-
Communication Address: 00.
-
Backlight: Set to 03.
-
LED: Set to 1-Wire.
4.
At the "Save Configuration" prompt, select Yes.
The display shows "Ready."
5.
As prompted by the command keypads, enter a valid cardholder PIN. If you have Biometric Verify
configured, present your finger to the Bioscrypt alternate reader to gain successful biometric
identification and access.
121.2

Hardware Revision and Firmware

The hardware revision can be determined in one of two ways:
Check the circuit board revision label located on the backside of the board.
Simultaneously press the center two keys of the top row on the keypad. The last character on the right of
the top line is the hardware revision.
In order for the command keypad to function properly, the following firmware is required:
LNL-CK rev. A uses firmware 1.3 or later.
LNL-CK rev. B uses firmware 1.50 or later.
LNL-CK rev. C uses firmware 1.50 or later. The command keypad currently ships with firmware
version 1.63. This firmware is loaded in the factory and cannot be upgraded in the field.
Note:
With firmware version 1.63, configuration options have changed. For more information, refer
to
Command Keypad Configuration
Reader interface module (firmware version 1.52.13 or later for the LNL-1300 Series 2, or firmware
version 1.57.5 or later for the LNL-1320 Series 2).