ISC Communications
c.
Flow. Flow control sets the local handshaking method for stopping serial input/output. The default
setting is 00. See
d.
Port No. The port number setting represents the source port number in TCP connections. It is the
number that identifies the channel for remote initiating connections. The default is port 10001. The
range is 1-65535. This should always be set to 3001 in order to communicate with third party
hardware devices.
e.
Connect Mode. Connect Mode defines how the unit makes a connection, and how it reacts to
incoming connections over the network. The default setting is C0 and should be used to
communicate with third party hardware devices.
The following may be left at default settings:
f.
Remote IP Address.
g.
Remote Port.
h.
DosConnMode.
i.
FlushMode.
j.
DisConnTime.
k.
SendChar 1.
l.
SendChar 2.
7.
When the configuration is complete, type 9 in the Change Setup menu to save your settings and exit.
The device will reboot. Or, to exit without saving any of your changes, type 8.
Using a Terminal Program
Use a terminal program to configure the device through a serial connection.
1.
Connect the device to a console terminal or PC running a terminal emulation program using the serial
port. The default serial port settings are 9600 baud, 8 bits, no parity, 1 stop bit, no flow control.
2.
Reset the device by cycling the unit's power (turning the power off and back on). Immediately upon
resetting the device, type xxx.
Note:
The easiest way to enter Setup Mode is to hold down the x key at the terminal (or emulation)
while resetting the unit. You must do this within three seconds of resetting the device.
3.
At this point, the screen display is the same as a telnet connection. To continue, go to step
Telnet.
41.8

Lantronix UDS-10/UDS100/UDS200/UDS1100

Step 1: Establish a serial connection with ETHLAN
With the power OFF on the UDS device, establish a serial communication from the UDS to the PC's serial
communication port, for example, using HyperTerminal.
1.
Start HyperTerminal.
2.
Select the correct PC port and change the communication settings to 9600 baud, 8 data bit, and parity
none.